3.1.2.1
ATEX Marking
3.1.3
Installing an RX3i CEP Carrier on a DIN-rail
The carrier mounts on a standard EN 50022, 35 x 7.5 mm DIN-rail. Conductive (unpainted)
finish is required for proper grounding.
For best resistance to vibration, the DIN-rail should be installed horizontally on a panel using
screws spaced approximately 15 cm (6 in) apart.
Figure 7: DIN Rail Mount
1.
2.
3.1.4
Removing an RX3i CEP Carrier from a DIN-rail
Figure 8: Extract from DIN Rail Mount
1.
2.
Installation & Mounting
Ex nA IIC T4 X 0C < Ta < 60C
With a small flathead screwdriver, pull out the two DIN-rail latches and stand the
carrier on the DIN-rail.
Push in the two DIN-rail latches so that the latches hold the DIN-rail.
If the carrier is attached to the panel with screws, remove the screws.
With a small flathead screwdriver, pull out the two DIN-rail latches and release the
latches from the DIN-rail, then remove the carrier.