Electrical installation
Installer and user reference guide
94
5 HP
RKXYQ5
X2M
TO IN/D
TO OUT/D
F1 F2
a1
a
b
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
a Sheathed + shielded cable (2 wires) (no polarity)
a1, a2 Connection of shield to earth
b Terminal board (field supply)
NOTICE
Shielded cable. Using shielded cable for the transmission wiring is mandatory for
5 HP, and optional for 8 HP.
5 HP
RKXYQ5
X2M
F1 F2
a1
a1, a2 Earth (use the screw delivered as accessory)
When using shielded cable:
In case of 5  HP (a1 and a2): Connect the shield to the earth of the compressor
unit and the heat exchanger unit.
In case of 8  HP (only a2): Connect the shield only to the earth of the heat
exchanger unit.
3 Connect the power supply as follows:
3N~ 50 Hz
380-415 V
L1 L2 L3
a
b
c
L1 L2 L3
N
a Earth leakage circuit breaker
b Fuse
c Power supply cable
4 Route the wiring through the frame, and fix the cables (power supply and
transmission wiring) with cable ties.
8 HP
RDXYQ5
RKXYQ8
X1M (A1P)
X2M
TO IN/D
TO OUT/D
F1 F2
F1 F2
a2
a
b
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
8 HP
RDXYQ5
RKXYQ8
X2M
X1M (A1P)
F1 F2
X1M
a2
X1M
RDXYQ8
X2M
F1 F2
a2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
RDXYQ8
X2M
a2