Daikin RDXYQ5T8V1B Installer And User Manual page 130

Heat pump for indoor installation
Table of Contents

Advertisement

22
|
Troubleshooting
Main code
Sub code
Installer and user reference guide
130
Cause
Warning: faulty wiring to Q1/Q2
Malfunction code: faulty wiring to Q1/
Q2
Too many indoor units are connected
to F1/F2 line
Bad wiring between outdoor and
indoor units
System mismatch. Wrong type of
indoor
units
combined
R407C,
RA,
etc).
malfunction
Heat exchanger unit malfunction
More than 1 heat exchanger unit
connected.
Improper type of indoor units are
connected.
Mismatch of compressor unit and
heat exchanger unit.
5 HP heat exchanger unit connected.
Auto
address
(inconsistency)
Mismatch of compressor unit and
heat exchanger unit.
Auto
address
(inconsistency)
Mismatch of compressor unit and
heat exchanger unit.
The stop valves of the compressor
unit are left closed.
The piping and wiring of the specified
indoor unit or heat exchanger unit are
not connected correctly to the
compressor unit.
Check Q1/Q2 wiring. Do NOT use Q1/
Q2.
Check Q1/Q2 wiring. Do NOT use Q1/
Q2.
Check indoor unit amount and total
capacity connected.
Check if other indoor units have
(R410A,
malfunction and confirm indoor unit
Indoor
unit
mix is allowed.
Check the transmission wiring to the
heat exchanger unit.
Check installation. Only 1 heat
exchanger unit can be installed.
Check the type of indoor units that
are currently connected. If they are
not proper, replace them with proper
ones.
Check if the compressor unit and heat
exchanger unit are compatible.
Check installation. Connect 8 HP heat
exchanger unit.
malfunction
Check if transmission wired unit
amount matches with powered unit
amount (by monitor mode) or wait till
initialisation is finished.
Check if the compressor unit and heat
exchanger unit are compatible.
malfunction
Check if transmission wired unit
amount matches with powered unit
amount (by monitor mode) or wait till
initialisation is finished.
Check if the compressor unit and heat
exchanger unit are compatible.
Open the stop valves on both the gas
and liquid side.
Confirm that the piping and wiring of
the specified indoor unit or heat
exchanger
correctly to the compressor unit.
Solution
unit
are
connected
RKXYQ5T8+8T7Y1B + RDXYQ5T8+8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12