18.2.7 Mode 1 (and default situation): Monitoring settings

RKXYQ5T8+8T7Y1B + RDXYQ5T8+8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
#
4
Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×" depends on
the current value, and the value
that you want to select.)
c: Enter the value in the system.
d: Confirm. The system starts
operating according to the setting.
5
Quit mode 2.
Example: 7‑segments display – Mode 2
(in case of 8 HP)
You can change the value of setting [2‑8] (= T
operation) to 4 (= 8°C) as follows:
#
1
Start from the default situation.
2
Select mode 2.
3
Select setting 8.
("X×" depends on the setting that
you want to select.)
4
Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×" depends on
the current value, and the value
that you want to select.)
c: Enter the value in the system.
d: Confirm. The system starts
operating according to the setting.
5
Quit mode 2.
In mode 1 (and in default situation) you can read out some information. What you
can read out differs depending on the model.
7‑LEDs display – Default situation (H1P OFF)
(in case of 5 HP)
You can read out the following information:
Action
e
Action
18
Configuration
|
Button/display
a
BS3 [1×]
b
BS2 [X×]
c
BS3 [1×]
d
BS3 [1×]
BS1 [1×]
target temperature during cooling
Button/display
BS1 [5 s]
BS2 [X×]
a
BS3 [1×]
b
BS2 [X×]
c
BS3 [1×]
d
BS3 [1×]
BS1 [1×]
Installer and user reference guide
105