Piping installation

16.4 Charging refrigerant

16.4.1 About charging refrigerant

Installer and user reference guide
82
Be sure to insulate the liquid and gas piping (for all units).
Use heat resistant polyethylene foam which can withstand a temperature of 70°C
for liquid piping and polyethylene foam which can withstand a temperature of
120°C for gas piping.
Reinforce the insulation on the refrigerant piping according to the installation
environment.
Ambient temperature
≤30°C
>30°C
If there is a possibility that condensation on the stop valve might drip down into
the indoor unit or into the heat exchanger unit through gaps in the insulation and
piping because the compressor unit is located higher than the indoor unit or
higher than the heat exchanger unit, this must be prevented by sealing up the
connections. See below figure.
a Insulation material
b Caulking etc.
The compressor unit is factory charged with refrigerant, but depending on the field
piping you have to charge additional refrigerant.
Before charging refrigerant
Make sure the compressor unit's external refrigerant piping is checked (leak test,
vacuum drying).
Typical workflow
Charging additional refrigerant typically consists of the following stages:
1
Determining how much you have to charge additionally.
2
Charging additional refrigerant (pre-charging and/or manual charging).
3
Filling in the fluorinated greenhouse gases label, and fixing it to the inside of
the compressor unit.
Humidity
75% to 80% RH
≥80% RH
b
a
Minimum thickness
15 mm
20 mm
RKXYQ5T8+8T7Y1B + RDXYQ5T8+8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12