Daikin RDXYQ5T8V1B Installer And User Manual page 61

Heat pump for indoor installation
Table of Contents

Advertisement

RKXYQ5T8+8T7Y1B + RDXYQ5T8+8T7V1B
VRV IV heat pump for indoor installation
4P499898-1B – 2021.12
c
b
e
d
d
a
a Personal computer or radio
b Fuse
c Earth leakage protector
d User interface
e Indoor unit
f Compressor unit
g Heat exchanger unit
In places with weak reception, keep distances of 3  m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for
power and transmission lines.
Service space. Mind the following requirements:
a
≥10
a Top view
b Front view
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
Do NOT install the unit in the following places:
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Note:
If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level mentioned in
Sound spectrum in the data book due to environmental noise and sound
reflections.
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
c
c
b
b
g
f
(mm)
b
≥10
15
Unit installation
|
(mm)
Installer and user reference guide
61

Advertisement

Table of Contents
loading

Table of Contents