Installation
3.4.2 Wire and Cable Access
•
Refer to through for wire routing and termination
locations.
•
Removable access knockout covers are provided
for cable connections (see Figure 3.13 and
3
3
Figure 3.14).
•
Access holes are provided for input power, motor
leads, and control wiring.
•
Run input power, motor wiring, and control
wiring in three separate conduits for isolation.
NOTE!
RUN INPUT POWER, MOTOR WIRING AND CONTROL
WIRING IN THREE SEPARATE METALLIC CONDUITS OR
RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION.
FAILURE TO ISOLATE POWER, MOTOR AND CONTROL
WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE
AND ASSOCIATED EQUIPMENT PERFORMANCE.
•
The drive always resides in the upper section of
the panel. Connections to the ECB and EMB2 are
in this area except on the P2 bypass panels.
•
Power connections are typically towards the
bottom side of the panel.
•
Control wiring should be isolated from power
components inside the unit as much as possible.
Danfoss has included hardware to allow for the
separation.
•
See the mechanical layout drawings in through
for connection details and recommended wire
routing.
3-16
Vertical Bypass/Non Bypass Panel
BYPASS PANEL CONDUIT ENTRY DIAGRAM
USE EITHER CONDUIT PLATE FOR CONVENIENCE
Figure 3.13 Bypass Panel Conduit Entry Diagram
CONTROL WIRES
POWER WIRES
Figure 3.14 Non Bypass Panel Conduit Entry Diagram
®
MG.13.A1.22 - VLT
is a registered Danfoss trademark
CONTROL WIRES
NON BYPASS PANEL CONDUIT ENTRY DIAGRAM
USE EITHER CONDUIT PLATE FOR CONVENIENCE
POWER WIRES