Installation; Tools Required; Drive Fuses - Trane VLT AQUA Drive FC 202 VLT AutomationDrive FC 301 Instruction Manual

Vertical bypass/non bypass panel
Table of Contents

Advertisement

Installation

3 Installation

3.1.1 Tools Required

In addition to the standard tool kit, the tools in Table 3.1
are recommended for installation of the panel.

3.1.2 Drive Fuses

To maintain UL, the drive fuses should be replaced only with the fuses specified in , , , and . If an alternate drive fuse is
desired please consult the factory. See the specifications label inside the cover of the unit for acceptable replacement drive
fuses. A sample of this data can be seen in Table 3.6
Panel
UL Motor
(FC102/202/322)
HP (KW)
Current
Non Bypass &
Bypass
7.5 (5.5)
24.2
10 (7.5)
30.8
15 (11)
46.2
20 (15)
59.4
P3 - Non Bypass P4
25 (18.5)
74.8
- Bypass
30 (22)
88
40 (30)
114
50 (37)
143
60 (45)
169
Table 3.2 Drive Fuses 208 V
Vertical Bypass/Non Bypass Panel
208 V AC
Main Fuse
(FC102/202/322)
Danfoss (Bussman)
34035600 (LPJ-40-
SP)
34035700 (LPJ-50-
P2
SP)
34042800 (LPJ-70-
SP)
34042900 (LPJ-90-
P3
SP)
34043100 (LPJ-125-
SP)
34043200 (LPJ-150-
SP)
P4
34043300 (LPJ-175-
SP)
34042300 (LPJ-250-
SP)
P5
34042300 (LPJ-250-
SP)
®
MG.13.A1.22 - VLT
is a registered Danfoss trademark
Spreader bar capable of lifting up to 750 lbs.
Max diameter 0.5 in.
Forklift, crane, hoist or other lifting device capable of handling
up to 750 lbs. (Qualified device operator available for operating
the equipment.)
Metric Socket Set: 7 - 19mm
Socket Extensions: 4, 6, and 12 inch
Torx driver set: T10 - T40
Torque wrench: 6 - 375 lbs-in
Allen Wrenches:1/8, 3/16, 1/4, & 5/16 inches
Metric or English wrenches: 7 - 19mm
Table 3.1 Tools Required
Drive Fuse
Transformer Fuse
(FC102/202/322)
(FC102/202/322)
Danfoss (Bussman)
Danfoss (Bussman)
176F8953 (JJN-50)
176F8953 (JJN-50)
176F8955 (JJN-60)
176F8957 (JJN-80)
176F8960 (JJN-125)
176F8960 (JJN-125)
174N6538 (JJN-150)
34046200 (FNQ-
174N6839 (JJN-200)
R-1.25)
34046200 (FNQ-
174N6840 (JJN-250)
R-1.25)
TOOLS
Panel
Drive Fuse
(FC302)
(FC302) Danfoss
Non
(Bussman)
Bypass
176F8953
(JJN-50)
P2
176F8955
(JJN-60)
176F8957
(JJN-80)
P3
176F8960
(JJN-125)
176F8960
(JJN-125)
P4
174N6538
(JJN-150)
174N6839
(JJN-200)
P5
174N6840
(JJN-250)
3
3
3-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents