Daikin ERGA08DAV3 Installer's Reference Manual page 94

Hide thumbs Also See for ERGA08DAV3:
Table of Contents

Advertisement

2/9
Field settings table
Breadcrumb
Field code
Setting name
Room
└─ Antifrost
1.4.1
[2-06]
Activation
1.4.2
[2-05]
Room setpoint
└─ Setpoint range
1.5.1
[3-07]
Heating minimum
1.5.2
[3-06]
Heating maximum
Room
1.6
[2-09]
Room sensor offset
1.7
[2-0A]
Room sensor offset
Main zone
2.4
Setpoint mode
└─ Heating WD curve
2.5
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
2.5
[1-01]
High ambient temp. for LWT main zone heating WD curve.
2.5
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
2.5
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Main zone
2.7
[2-0C]
Emitter type
└─ Setpoint range
2.8.1
[9-01]
Heating minimum
2.8.2
[9-00]
Heating maximum
Main zone
2.9
[C-07]
Control
2.A
[C-05]
Thermostat type
└─ Delta T
2.B.1
[1-0B]
Delta T heating
└─ Modulation
2.C.1
[8-05]
Modulation
2.C.2
[8-06]
Max modulation
└─ Shut off valve
2.D.1
[F-0B]
During thermo
Additional zone
3.4
Setpoint mode
└─ Heating WD curve
3.5
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
3.5
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
3.5
[0-02]
High ambient temp. for LWT add zone heating WD curve.
3.5
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
Additional zone
3.7
[2-0D]
Emitter type
└─ Setpoint range
3.8.1
[9-05]
Heating minimum
3.8.2
[9-06]
Heating maximum
Additional zone
3.A
[C-06]
Thermostat type
└─ Delta T
3.B.1
[1-0C]
Delta T heating
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
Space heating OFF temp
Space heating / cooling
4.4
[7-02]
Number of zones
4.5
[F-0D]
Pump operation mode
4P495259-1B - 2019.06
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
0: Disabled
1: Enabled
4~16°C, step: 1°C
12°C
12~18°C, step: 0,5°C
12°C
18~30°C, step: 0,5°C
30°C
-5~5°C, step: 0,5°C
0°C
-5~5°C, step: 0,5°C
0°C
0: Fixed
2: Weather dependent
-40~5°C, step: 1°C
-10°C
10~25°C, step: 1°C
15°C
[9-01]~[9-00], step: 1°C
35°C
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
0: Underfloor heating
1: Fancoil unit
2: Radiator
15~37°C, step: 1°C
25°C
[2-0C]=2:
37~65, step: 1°C
55°C
[2-0C]≠2:
37~55, step: 1°C
55°C
0: LWT control
1: Ext RT control
2: RT control
0: -
1: 1 contact
2: 2 contacts
3~10°C, step: 1°C
5°C
0: No
1: Yes
0~10°C, step: 1°C
5°C
0: No
1: Yes
0: Fixed
2: Weather dependent
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
[9-05]~[9-06]°C, step: 1°C
50°C
10~25°C, step: 1°C
15°C
-40~5°C, step: 1°C
-10°C
0: Underfloor heating
1: Fancoil unit
2: Radiator
15~37°C, step: 1°C
25°C
[2-0D]=2:
37~65, step: 1°C
55°C
[2-0D]≠2:
37~55, step: 1°C
55°C
0: -
1: 1 contact
2: 2 contacts
3~10°C, step: 1°C
5°C
14~35°C, step: 1°C
22°C
0: 1 LWT zone
1: 2 LWT zones
0: Continuous
1: Sample
2: Request
Installer setting at variance with
default value
Date
Value
(*1) *3V_
(*2) *6V_
(*3) *9W