Code
[4.5]
[F–0D]
Pump operation mode:
▪ 0
operation, regardless of thermo ON or
OFF condition. Remark: Continuous
pump operation requires more energy
than
operation.
b
b
▪ a: Space heating control
▪ b: Off
▪ c: On
▪ d: Pump operation
[4.5]
[F-0D]
▪ 1 Sample: The pump is ON when there
is heating demand as the leaving
water temperature has not yet reached
the desired temperature yet. When
thermo OFF condition occurs, the
pump runs every 3 minutes to check
the water temperature and demand
heating if necessary. Remark: Sample
is ONLY available in leaving water
temperature control.
a
b
d
g
b
▪ a: Space heating control
▪ b: Off
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
▪ 2 Request: Pump operation based on
[4.5]
[F-0D]
request. Example:
thermostat and thermostat creates
thermo ON/OFF condition. Remark:
NOT
temperature control.
a
b
d
e
b
▪ a: Space heating control
▪ b: Off
▪ c: On
▪ d: Heating demand (by external
▪ e: Pump operation
ERGA04~08DAV3(A) + EHVZ04+08S18+23DA +
EHVZ04+08S18+23DJ
Daikin Altherma 3 R F
4P495249-1B – 2019.06
Description
Continuous:
Continuous
pump
sample
or
request
pump
a
c
c
d
c
e
f
c
Using a room
available
in
leaving
water
c
c
b
c
room
thermostat
or
room
thermostat)
Unit type
In this part of the menu it can be read out which type of unit is used:
#
Code
[4.6]
N/A
Unit type:
▪ 1 Cooling only
▪ 2 Heating only
▪ 3 Reversible
Pump limitation
The pump speed limitation for the main zone [9‑0E] and additional
zone [9‑0D] defines the maximum pump speed. In normal
conditions, the default setting should NOT be modified. The pump
speed limitation will be overruled when the flow rate is in the range
of the minimum flow (error 7H).
#
Code
[4.7]
[9-0D]
Pump limitation Additional zone:
▪ 0: No limitation
▪ 1~4: General limitation. There is
limitation
required delta T control and comfort
are NOT guaranteed.
▪ 5~8: Limitation when no actuators.
When there is no heating output, the
pump speed limitation is applicable.
When there is heating output, the
pump speed is only determined by
delta  T in relation to the required
capacity. With this limitation range,
delta  T is possible and the comfort is
guaranteed.
Pump limitation Main zone:
[4.8]
[9-0E]
▪ 0: No limitation
▪ 1~4: General limitation. There is
limitation
required delta T control and comfort
are NOT guaranteed.
▪ 5~8: Limitation when no actuators.
When there is no heating output, the
pump speed limitation is applicable.
When there is heating output, the
pump speed is only determined by
delta  T in relation to the required
capacity. With this limitation range,
delta  T is possible and the comfort is
guaranteed.
The maximum values depend on the unit type:
[9-0D]=0
a (kPa)
b (l/min)
8 Configuration
Description
Description
in
all
conditions.
The
in
all
conditions.
The
[9-0D]=5
a (kPa)
b (l/min)
Installer reference guide
57