Daikin ERGA08DAV3 Installer's Reference Manual page 82

Hide thumbs Also See for ERGA08DAV3:
Table of Contents

Advertisement

12 Troubleshooting
Error code
Detailed error
code
E3
00
E5
00
E6
00
E7
00
E8
00
EA
00
H0
00
H3
00
H6
00
H8
00
H9
00
F3
00
F6
00
FA
00
JA
00
J3
00
J6
00
J6
07
L3
00
L4
00
L5
00
P4
00
U0
00
U2
00
U7
00
Error codes of the indoor unit
Error code
Detailed error
code
7H
01
7H
04
Installer reference guide
82
Description
OU: Actuation of high
pressure switch (HPS)
OU: Overheat of inverter
compressor motor
OU: Compressor startup
defect
OU: Malfunction of outdoor
unit fan motor
OU: Power input overvoltage
OU: Cool/heat switchover
problem
OU: Voltage/current sensor
problem
OU: Malfunction of high
pressure switch (HPS)
OU: Malfunction of position
detection sensor
OU: Malfunction of
compressor input (CT)
system
OU: Malfunction of outdoor
air thermistor
OU: Malfunction of
discharge pipe temperature
OU: Abnormal high pressure
in cooling
OU: Abnormal high pressure,
actuation of HPS
OU: Malfunction of high
pressure sensor
OU: Malfunction of
discharge pipe thermistor
OU: Malfunction of heat
exchanger thermistor
OU: Malfunction of heat
exchanger thermistor
OU: Electrical box
temperature rise problem
OU: Malfunction of inverter
radiating fin temperature
rise
OU: Inverter instantaneous
overcurrent (DC)
OU: Malfunction of
radiating fin temperature
sensor
OU: Shortage of refrigerant
OU: Defect of power supply
voltage
OU: Transmission
malfunction between main
CPU- INV CPU
Description
Water flow problem
Water flow problem during
domestic hot water
production
Error code
Detailed error
code
7H
05
7H
06
7H
07
80
00
81
00
81
01
89
01
89
02
89
03
8F
00
8H
00
8H
01
8H
02
8H
03
AA
01
AA
02
AH
00
AJ
03
C0
00
C0
01
C0
02
C4
00
CJ
02
EC
00
EC
04
H1
00
HC
00
HC
01
HJ
10
JA
17
U3
00
U4
00
ERGA04~08DAV3(A) + EHVZ04+08S18+23DA +
Description
Water flow problem during
heating/sampling
Water flow problem during
cooling/defrost
Water flow problem. Pump
deblocking active
Returning water temperature
sensor problem
Leaving water temperature
sensor problem
Mixed water thermistor
abnormality.
Heat exchanger frozen
Heat exchanger frozen
Heat exchanger frozen
Abnormal increase outlet
water temperature (DHW)
Abnormal increase outlet
water temperature
Overheating mixed water
circuit
Overheating mixed water
circuit (thermostat)
Overheating water circuit
(thermostat)
Backup heater overheated
External backup heater
overheated
Tank disinfection function
not completed correctly
Too long DHW heat-up time
required
Water flow detected while pump
is OFF
Flow switch malfunction
Flow switch malfunction
Heat exchanger temperature
sensor problem
Room temperature sensor
problem
Abnormal increase tank
temperature
Tank preheating
External temperature sensor
problem
Tank temperature sensor
problem
Second tank temperature
sensor problem
Water pressure sensor
abnormality
Refrigerant pressure sensor
abnormality
Underfloor heating screed
dryout function not
completed correctly
Indoor/outdoor unit
communication problem
EHVZ04+08S18+23DJ
Daikin Altherma 3 R F
4P495249-1B – 2019.06

Advertisement

Table of Contents
loading