Honeywell Notifier NFW-100X Manual page 15

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Specifications
Remote Sync Output - TB8
Remote power supply synchronization output
24 VDC nominal special application power
Maximum current is 350 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit
Programmable Class A or Class B wiring
Secondary ANN-BUS - TB10
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Annunciators require non-resettable power
Primary ANN-BUS - TB9
Class A or Class B wiring
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Class A wiring uses Terminal 3 (+/A Return) and Terminal 4 (-/B Return)
Annunciators require non-resettable power
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available
from the FACP.
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable or
Nonresettable Power
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
1.0 amp max
per circuit
1.0 amp max
per circuit
5
6
2.5 amps max
NAC #1
per circuit
TB5
2.5 amps max
NAC #2
per circuit
TB6
2.5 amps max
NAC #3
per circuit
TB7
2.5 amps max
NAC #4
per circuit
TB8
Remote
0.35 amp max
Synchronization
per circuit
Output
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability without PWRMOD24 Option
Standby
2.0 amps max
per panel
Alarm
3.0 amps max*
per panel
*Note: When the option module
PWRMOD24 is installed, an
additional 3.0 amps of alarm power is
available across NAC #1 through
NAC #4 and the remote
synchronization output expanding
max power to 6.0 amps
Product Description
15