Installation
(1 of 5 using the legacy NFV panel) can be generated over the selected speaker circuit. Any fault in the NFC-50/100 audio system is sent
to the FACP via the FACP Data Bus and is indicated as an annunciator fault on the FACP display. A fault at the NFV-25/50ZS Series
panel will cause the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault.
For speaker circuit mapping and audio message assignment, refer to "Zone Message" on page 70. Also, refer to "Programmed Activa-
tion by FACP" in chapter 3 of the NFC-50/100 Instruction Manual (Doc. LS10001-001NF-E) or Appendix D, "Programmed Activation
by FACP" in the NFV-25/50ZS Series Instruction Manual (Doc. 52290).
Connect the NFC-50/100 panel's FACP Data Bus at TB13 to TB9 on the NFW-100X FACP.
The only connection between the FACP and NFV-25/50ZS Series audio panel is a pair of communication wires connected between the
A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals 2 & 3 of the NFV-ZPMK module on the audio panel.
48
NFC-50/100
to other ANN
devices
Figure 2.32 FACP Connection to NFC-50/100 Series Audio Panel
+ -
A (+)
Figure 2.33 FACP Connection to NFV-25/50ZS(T) Series Audio Panel (Legacy)
A
B
NFW-100X
on NFV-25/50ZS(T) Series
S1
ON
TENS ONES
ON
1 2 3 4 5 6 7 8
S3
S2
Primary ANN-BUS
B (-)
NFW-100X
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Automatic Audio Panel Control
NFV-ZPMK