Nac (Notification Appliance Circuit) - Honeywell Notifier NFW-100X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Master Programming Level
Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be programmed for either PAS or Pre-
signal operation. Refer to"Edit Detector" on page 54 for programming details.
Waterflow Delay
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-
five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the
Delay Screen which will indicate the new delay time.
AC Loss Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
Timer Screen #2
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central sta-
tion.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour
delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1. Refer to the table on page 49 for permissi-
ble settings.
NOTE: Upon the loss of AC power at the control panel, relays programmed for 'AC Loss' will transfer immediately, regardless of the AC
Loss Delay setting. If no trouble exists at the panel other than AC Loss, the System Trouble relay will delay its activation for the duration of
the AC Loss Delay setting.
Control Module Delay
TIMER
1=AC LOSS DELAY
2=CTRL MOD DLY
Timer Screen #2
A flashing cursor will appear in the lower left corner of the display. Type the three digit control module delay in seconds (000 to 180 sec-
ond delay). When the third digit is entered, the display will return to the Delay Screen which will indicate the new delay time. Refer to
the table on page 49 for permissible settings.

NAC (Notification Appliance Circuit)

SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays
of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a
Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing
Timer Screen #1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS

Waterflow Delay Screen
The reporting of a loss of AC power to a central station can be delayed by programming the length of the
desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2 to display the
following:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
AC LOSS DELAY
RANGE 00-23

AC Loss Delay Screen #2
The control module delay feature, if enabled, will delay activation of a control module after being triggered
by an alarm condition. Pressing 2 while viewing Timer Screen #2 will display the following:
CTRL MOD DELAY
RANGE 0-180 SECONDS

Control Module Delay Screen
The options for the NACs on the control panel main circuit board can be configure by pressing 2 while
viewing System Setup Screen #2. The following screens will be displayed:
NACS
1=NAC 1
2=NAC 2
NAC Selection Screen
3=NAC 3
4=NAC 4
Programming
75

Advertisement

Table of Contents
loading

Table of Contents