NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Cut Jumper JP3 on the NFW-100X main circuit board to supervise placement of the 4XTM module.
2.
Refer to "4XTM Transmitter Module Installation" on page 31 for detailed information.
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
Figure C.2 Remote Station Connection Using 4XTM Module
NFPA Standard-Specific Requirements
Polarity Shown is
+
-
Normal Standby
+
Power-limited
-
Ω
(Dummy load with a 4.7K
, ¼ watt resistor
when no connection is made)
4XTM Transmitter Module
139