PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2

Function Keys

The ES-50X keypad has 4 programmable function keys. These keys can be programmed to allow rapid disable/enable of various fire panel
inputs and outputs during scheduled maintenance. Pressing any function key results in a trouble signal at the panel. Pressing 1 on System
Setup Screen #1 displays the following:
FUNCTION KEYS
1=F1
3=F3
2=F2
4=F4
Function Keys Screen
To Enable or Disable the Function Key, press the 1 key while viewing the Function Keys Screen #1. Each press of the key will toggle the
screen between Key Enabled Yes and Key Enabled No.
Pressing 2 key while viewing the Function Keys Screen #1 allows the user to select individual zones that the Function Key will control.
Pressing 3 assigns all zones to the selected Function Key.
Each function key can be assigned to control any of the 2 onboard NAC circuits on the ES-50X. By pressing the 2 key while viewing the
Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing 1 or 2 toggles the screen between Yes (controlled by function key) and No (not controlled by function key) for each onboard NAC
circuit.
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB
Function Keys Screen #2
SYSTEM SETUP
1=FUNCTION KEYS

2=BANNER

3=TIME-DATE
System Setup Screen #1
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be dis-
played:
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
System Setup Screen #4
1=F1
2=F2
Select 1, 2, 3, or 4 to program the corresponding Function Key. The following screens display for each Function
Key where "(X)" represents the number of the key chosen.
F(X) KEY OPERATION
1=KEY ENABLED
2=ZONES
3=ALL ZONES
Function Keys Screen #1
1=NAC 1
The Remote Synchronization (TB8 on the FACP's main circuit board) can also be disabled through program-
ming of a function key. To disable remote synchronization, press the 3 key while viewing the Function Keys
NO
Screen #2. Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync Disb No.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by using
the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed:
SYSTEM SETUP
1=TIMERS
2=NACS
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB NO
24HR
3=REM SYNC ENAB YES
ENGLISH
System Setup Screen #5
FUNCTION KEYS
3=F3
4=F4
Function Keys Screen
F(X) KEY OPERATION
NO
1=NACS
2=DIS REM DISB
Function Keys Screen #2
F(X) NACS
N
2=NAC 2 Y
Function Keys Screen
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
NO
NO
Programming
69