Zone TEST :
This function allows to start the Walk-Test procedure for a selected zone.
This procedure is composed of 2 folders where the editing function previously explained is applied to enter data.
E
n
a
b
l
i
n
g
o
f
a
z
o
n
e
f
o
r
E
n
a
b
l
i
n
g
o
f
a
z
o
n
e
f
o
r
Enter the zone number for which the test
function must be activated.
(0 = inactive test zone)
CBE Enabling
By selecting CBE Enable.: YES
in case of alarm from the test zone devices
CBEs associated with them are activated
To change one parameter in this folder select the parameter through the arrow keys (the characters of the
selected field are in Reverse), press the enter key
at the end press the enter key
O
u
t
p
u
t
s
e
l
e
c
t
i
o
n
O
u
t
p
u
t
s
e
l
e
c
t
i
o
n
In the subsequent programming folder the output to be activated in case of alarm from a device of the test zone
is selected.
To change one or several parameters in this folder select the parameter through the arrow keys (the
characters of the selected field are in Reverse), press the enter key
the parameter; at the end press the enter key
LED TEST:
By selecting through the arrow keys the Led item and by pressing the enter key
unit performs the lamp-test function (all the control unit leds flash for some seconds)
LCD TEST:
By selecting through the arrow keys the LCD item and by pressing the enter key
unit performs the display test.
BUZZER TEST:
AM_8200
AM82000_manu-prog-ENG
t
h
e
t
e
s
t
f
u
n
c
t
i
o
n
t
h
e
t
e
s
t
f
u
n
c
t
i
o
n
to confirm the datum.
It will sound intermittently
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
and use the arrow keys to change the parameter;
In the "Select" field you can select one of the following
items:
NONE = in case of alarm from the test zone it does not
activate outputs.
SOUNDER = in case of alarm both the Siren output
and all the output modules programmed through Type
– ID "HORN" are activated at each alarm event from
the test zone
The activation duration is 3 sec.
MODULE
output module programmed in the " Ind. Mod." Item
is activated and at each alarm event it will be active for
3 sec.
and use the arrow keys to change
to confirm the datum.
= in case of alarm from the test zone the
to confirm, the control
to confirm, the control
NOTIFIER ITALIA