Ip Address Table Write - Omron CS1W-ETN11 Operation Manual

10base-5, 10base-t ethernet units
Hide thumbs Also See for CS1W-ETN11:
Table of Contents

Advertisement

Command/Response Reference

11-3-19 IP ADDRESS TABLE WRITE

Command Block
Response Block
Parameters
Number of Records
(Command)
IP Address Table Records
(Command)
Precautions
Response Codes
Writes the IP address table.
27
50
6 bytes
Command
Number of
IP address
code
records
table records
27
50
Command
Response
code
code
The number of records to write is specified between 0000 and 0020 (0 to 32
decimal) in the command. If this value is set to 0, the IP address table will be
cleared so that no records are registered.
Specify the IP address table records. The number of records specified must
be provided. The total number of bytes in the IP address table records is cal-
culated as the number of records x 6 bytes/record. The configuration of the
6 bytes of data in each record is as shown in the following diagram.
1
FINS Node Number
Node number for communications via the FINS command (hexadecimal).
IP Address
IP address used by TCP/IP protocol (hexadecimal).
The new I/O address table records will not be effective until the PC is
restarted or the Ethernet Unit is reset.
An error response will be returned if the IP address conversion method in the
system mode settings is set for automatic generation.
Response code
0000
Normal (echo reply received from the remote node)
1001
Command too large
1002
Command too small
1003
The number of records specified does not match the sent data
length.
110C
The number of records is not between 0 and 32.
The FINS node number is not between 1 and 126
The IP address is 0.
2307
IP address conversion method is set for automatic generation.
6 bytes
IP address
table records
00
FINS node
IP address
number
Description
Section 11-3
6 bytes
237

Advertisement

Table of Contents
loading