Creating Routing Tables

3-8

Creating Routing Tables

3-8-1

Routing Table Overview

46
explanation of how to create an I/O table using a CX-Programmer, refer to the
CX-Programmer User's Manual.
Use the following procedure to create the I/O table.
Note With the CJ Series, it is necessary to create an I/O table only when I/O alloca-
tion is performed by the user. With the CS Series, it is always necessary to
create an I/O table.
Initial screen
000000 I/O TBL ?
CHG
000000 I/O TBL
WRIT
????
000000CPU BU ST?
0:CLR 1:KEEP
000000 I/O TBL
WRIT OK
When the FINS communications service is used, routing tables must be cre-
ated in advance. Routing tables are required in the following circumstances.
• When the FINS communications service is used on an Ethernet network
(including when communications are only carried out between FA net-
works via an Ethernet network).
• When there are multiple Communications Units mounted to the PC, and
socket services are requested by executing the CMND(490) instruction.
If neither of these circumstances apply, then a routing table is not required. In
that case, proceed to 3-9 System Setup.
The routing table is required not only for nodes communicating via the FINS
communications service but for all relay nodes on the network.
The routing tables describe the transmission path for FINS messages when
the FINS communications are used. It consists of two tables: A local network
table and a relay network table.