Auxiliary Area Data - Omron CS1W-ETN11 Operation Manual

10base-5, 10base-t ethernet units
Hide thumbs Also See for CS1W-ETN11:
Table of Contents

Advertisement

The following table and descriptions cover the words and bits in the Auxiliary Area of PC memory that are
related to the Ethernet Unit.
Read-only Bits/Words
Word(s)
Bit(s)
A202
A20200 to
Communications
A20207
Port Enabled Flags
A203 to
---
Communications
A210
Port Completion
Codes
A219
A21900 to
Communications
A21907
Port Error Flags
A302
A30200 to
CPU Bus Unit
A30215
Initializing Flags
A402
A40203
CPU Bus Unit Set-
ting Error Flag
(Non-fatal error)
A40207
CPU Bus Unit Error
Flag
(Non-fatal error)
A403
A40300 to
Memory Error
A40308
Location
Appendix E

Auxiliary Area Data

Name
Bits A20200 to A20207 turn ON when a network
instruction (SEND, RECV, CMND, or PMCR) can be
executed with the corresponding port number. Bits
00 to 07 correspond to communications ports 0 to 7.
These words contain the completion codes for the
corresponding port numbers when network
instructions (SEND, RECV, CMND, or PMCR) have
been executed. Words A203 to A210 correspond to
communications ports 0 to 7.
Bits A21900 to A21907 turn ON when an error
occurred during execution of a network instruction
(SEND, RECV, CMND, or PMCR). Bits 00 to 07
correspond to communications ports 0 to 7.
Bits A30200 through A30215 turn ON while the
corresponding CPU Bus Units (Units #0 through
#15, respectively) are initializing. The bits will turn
ON either when power is turned ON or when a CPU
Bus Unit Restart Bit (A50100 to A50115) is turned
ON.
Bit A40203 is turned ON when the CPU Bus Units
actually installed differ from the Units registered in
the I/O table. The ERR/ALM indicator on the front of
the CPU Unit will flash, but CPU operation will
continue.
The unit number of the CPU Bus Unit involved is
stored in word A427.
Bit A40207 is turned ON when an error occurs
during the transmission of data between the CPU
and CPU Bus Units. The ERR/ALM indicator on the
front of the CPU Unit will flash, but CPU operation
will continue. The Unit where the error occurred will
stop.
The unit number of the CPU Bus Unit involved is
stored in word A422.
When a memory error occurs, the Memory Error
Flag (A40115) is turned ON and one of the following
flags is turned ON to indicate the memory area
where the error occurred.
A40300: User program
A40304: PC Setup
A40305: Registered I/O Table
A40307: Routing Table
A40308: CPU Bus Unit Settings
The ERR/ALM indicator on the front of the CPU Unit
will light and CPU operation will stop.
Function
Settings
0: Network communi-
cations running
1: No network com-
munications running
0000: No error
Not 0000: Error code
0: Normal end
1: Error end
0: Not initializing
1: Initializing (System
will automatically turn
the flag OFF when ini-
tialization has been
completed.)
0: No setting error
1: Setting error
0: No unit number
error
1: Unit number error
0: Normal
1: Error
267