Udp Receive Request - Omron CS1W-ETN11 Operation Manual

10base-5, 10base-t ethernet units
Hide thumbs Also See for CS1W-ETN11:
Table of Contents

Advertisement

Command/Response Reference
Response Codes
Results Storage Area Response Codes

11-3-10 UDP RECEIVE REQUEST

Command Block
Response Block
Results Storage
Format
Parameters
UDP Socket Number
(Command)
Results Storage Area
(Command)
224
the socket specified in the UDP socket number, and send packets are distrib-
uted from the UDP socket to this port. The port number specified as the FINS
UDP port number (default value 9600) cannot be used.
Response code
0000
Normal
0105
Local IP address setting error
0302
CPU Unit error; execution not possible.
1001
Command too large
1002
Command too small
1100
UDP socket number is out of range.
Local UDP port number is 0.
1101
The variable type for the results storage area is out of range.
1103
Non-zero bit address specified for the results storage area.
220F
Specified socket is already open or is being closed.
2211
High traffic at Unit; cannot execute service.
Response code
0000
Normal
003E
Internal buffer cannot be reserved due to high receive load
(ENOBUFS).
0049
Duplicate UDP port number (EADDRINUSE).
Requests that data be sent from a UDP socket.
27
02
Command
UDP
Results storage area
code
socket
number
27
02
Command
Response
code
code
Results
Source IP
storage
address
response
code
The UDP socket number to receive data specified as 2 bytes between 1 and
8.
The area in which the results of the command execution are stored. The first
byte specifies the memory area and data type (variable type). The 2nd to 4th
bytes specify the beginning address of the results storage area. Refer to
page 216 for details about the variable types and addresses that can be spec-
ified.
Description
Description
Number of
Timeout
reception
value
bytes
Source
Number of
UDP port
reception
number
bytes
Section 11-3
Received bytes
Received data