Step 17: Project Commissioning Checklist - Trane Tracer Concierge Installation Instructions Manual

Hide thumbs Also See for Tracer Concierge:
Table of Contents

Advertisement

Step 17: Project Commissioning Checklist

Verify:
Display main screen shows all the intended zones.
Date and time are correct.
Schedules are listed correctly.
Graphics are listed correctly and appear correctly.
Contact information is correct.
Setpoint control on the display:
Adjust setpoints to max/min. The adjustment buttons are grayed out when the limit
is reached.
Verify rooftop control to setpoint. Use the System Controller web interface to verify
that the setpoint is sent to the rooftop.
Verify override control at the display:
1. In the System Controller web interface, override a zone/area, or a space not in an area,
to unoccupied at level 14 with a 15 minute timer. This is a higher priority than the
schedule (level 15), but not as hight as the display (level 13). The override should take
affect over the schedule, but the display will be able to control.
2. In Tracer Concierge, tap the power icon to override the area occupied. Verify that the
area occupies and that the display dives a 2 hour timer.
3. Tap the Reset icon to verify that Tracer Concierge resets the timer to 2 hours.
4. Tap X to verify that Tracer Concierge cancels the override.
5. In the System Controller Web interface, release the override made in Step 1 or wait
for the 15 minute timer to run out. Verify that you leave the system with the zone
controlled by the schedule as normal operation intends.
Verify remote access (if applicable) with Tracer Ensemble, System Controller web
interface, and/or Tracer BAS Operator Suite mobile application.
Backup System Controller and any unit controllers.
BAS-SVN208G-EN
Step 17: Project Commissioning Checklist
21