Installation Instructions Tracer® Concierge™ System Model Numbers: BMTC015ABC012000, BMTC015CAC012000 BMTC030ABC012000, BMTC045CBC012000 BMTC015CBC012000, BMTC060CBC012000 BMTC030CBC012000, BMTC030CAC012000 SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
Page 2
CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs. Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules.
Page 3
Non-Trane personnel should always follow local regulations. Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Step 2: Install BCI-R and Air-Fi® Wireless (Optional) ....6 Step 3: Install the UC400 2H/2C and Air-Fi® Wireless for Non-Trane RTUs Step 4: Install the UC210 Bypass Damper and Air-Fi®...
Installation Step 2: Install BCI-R and Air-Fi® Wireless (Optional) If required for this site, install the BCI-R and Air-Fi® Wireless. Use the wiring harness provided with the BCI-R to wire from the RTRM(J-4, 5-pin connector) to BCI-R(J-1, 4-pin connector).For more information see Installation guide BACnet™...
Step 3: Install the UC400 2H/2C and Air-Fi® Wireless for Non-Trane RTUs If required for this site, install the UC400 2H/2C and Air-Fi® Wireless on non-Trane equipment. For more information, see Tracer UC400 Pre-programmed for RTU or Heat Pump (X39641251-01B). The point list below is for your convenience.
Installation Step 4: Install the UC210 Bypass Damper and Air-Fi® Wireless If required for this site, install the UC210 Bypass Damper. See the installation documentation. The point list below is for your convenience. Table 3. I/O points Location Function Pressure Input Duct Static Pressure Local AI3/DAT Discharge Air Temperature (Optional)
Page 9
Installation Figure 3. Unit controller rotary addressing On WCS zone sensors, set: • GRP and NET to 1 and 1 • Address the WCS to match the corresponding unit controller To enter the WCS address settings, press and hold the address button for 3 seconds. Figure 4.
Installation Step 5: Install Tracer Concierge Panel Important: Do not power the display until instructed to do so in Installation Instructions. Dimensions and Clearances Figure 6, p. 11 shows the internal enclosure dimensions and minimum clearances. Select a mounting location that provides adequate space for the minimum clearance dimensions. Refer to Figure 7, p.
Page 11
Installation Figure 6. Enclosure minimum clearances with cover 12 in. (305 mm) 36 in. (914 mm) 24 in. 12 in. (610 mm) (305 mm) 12 in. (305 mm) 50 in. (1270 mm) Recommended Figure 7. External dimensions Knockouts for 1 inch (25 mm) and .75 inch (19 mm) conduit Knockout for .50 inch (13 mm) conduit (for AC wiring) Knockout for .75 in (19 mm) conduit...
Installation: U.L. 840: Category 3 Pollution: U.L. 840: Degree 2 Important: The Tracer Concierge Panel enclosure must be installed indoors. Trane recommends locating the enclosure: • Where service personnel have easy access. • In areas that restrict public access to minimize tampering or vandalism.
Page 13
Installation NOTICE Use Copper Conductors Only! Failure to use copper conductors could result in equipment damage as the equipment was not designed or qualified to accept other types of conductors. To ensure proper operation of the controllers, install the power supply circuit in accordance with the following guidelines: •...
Installation Figure 8. AC wiring Install Enclosure Door 1. Unpack the door and check for any missing or damaged parts. 2. Position the door at a 90 degree angle from the enclosure, as shown below. BAS-SVN040B-EN...
Page 15
Installation Figure 9. Installing the enclosure door 3. Align the hinge pegs on the door with the hinge holes on the enclosure and gently lower the door until it rests securely in the hinge holes. 4. Verify that the door swings freely on the hinges and that the magnetic latches hold the door securely when it is closed.
Installation Step 6: Wire I/O The field I/O wiring is specific for each application. Module Rotary Dial Terminals Name Notes Outside Air XM30 UI/AO 1 Thermistor Temperature XM30 UI/AO 2 Not used XM30 UI/AO 3 Not used XM30 UI/AO 4 Not used Must be wired as dry contact;...
Installation Figure 10. Back of display with ethernet and power connector Step 8: System Startup Important: Ensure all equipment and Air-Fi® Wireless are powered and operating before proceeding. This is because the network will be formed on power up of Tracer Concierge Controller.
Installation 3. Connect the Ethernet cable for customer’s network to Ethernet Port 1. Step 9: Display Setup 1. Power on the display by pressing the power button on the back of the display. 2. Follow the steps in the Setup Wizard. See the Tracer Concierge Installation, Operation, and Maintenance Guide (BAS-SVX074) for details.
Installation Step 10: Installing the Wi-Fi Router Note: The Concierge Controller in its pre-wired enclosure should be operating and communicating to all the equipment before installing the Wi-Fi router. The optional Wi-Fi router is used when the Concierge Controller and the Concierge Display cannot both be on the customer's Wi-Fi network.The router (Order Number: X13651632010) is set up to allow the Concierge Controller and the Display to communicate on their own small (2 device) Wi- Fi network.
Installation Agency Listing and Compliance United States Compliance (Enclosure and modules are UL Listed separately) UL Listed — UL 916 Energy Management Accessory Canadian Compliance (Enclosure and modules are CUL Listed separately) CUL Listed — CSA C22.2 No. 205 BAS-SVN040B-EN...
Page 24
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.