Installation Instructions
Tracer Concierge™ System
Part 2 of 2: Setup for Small Buildings
Order Numbers:
Please retain this document for future reference.
Only qualified personnel should install and service the equipment. The installation,
starting up, and servicing of heating, ventilating, and air-conditioning equipment can
be hazardous and requires specific knowledge and training. Improperly installed,
adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
August 2020
X13760358001 Tracer 10-inch Display
SAFETY WARNING
BAS-SVN208G-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane Tracer Concierge

  • Page 1 Installation Instructions Tracer Concierge™ System Part 2 of 2: Setup for Small Buildings Order Numbers: X13760358001 Tracer 10-inch Display Please retain this document for future reference. SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
  • Page 2 Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
  • Page 3 Non-Trane personnel should always follow local regulations. Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
  • Page 4: Table Of Contents

    Table of Contents Installation Order ..........5 Step 9: Verify Package Contents .
  • Page 5: Installation Order

    Installation Order Installation Order • Hardware setup (Steps 1-8). See Tracer Concierge System Part 1 of 2: Hardware Setup (BAS-SVN135*-EN). • Setup System Controller and display (Steps 9-17, this document). Step 9: Verify Package Contents Table 1. Packaged contents Item Quantity 10.1 in.
  • Page 6: Step 11: Air-Fi ® Wireless Setup

    This location provides the best overall sensor and communication link quality. Trane has special recommendations for coordinator and repeater placement on sites without VAV boxes. We recommend relocating the WCI below the roof deck in a serviceable location on these applications.
  • Page 7: Air-Fi ® Addressing

    ® Step 11: Air-Fi Wireless Setup sensor. • If mounting onto sheetrock or plaster, use the plastic threaded anchors (pre-drilling holes is not usually necessary) and the two M3.5 x 20 mm mounting screws. • For mounting onto an electrical junction box, use the two 6-32 x 3/4 in. screws. ®...
  • Page 8: Wcs: Network Joining And Controller Association

    ® Step 11: Air-Fi Wireless Setup Note: The network must be open for a WCS to join the network, but does not need to be open for the WCS to be manually assigned to a controller. WCS: Network Joining and Controller Association After addresses are set, the WCS will immediately attempt to join the network and associate with the controller.
  • Page 9: Step 12: Tracer Uc210 Setup For Changeover Systems

    Step 12: Tracer UC210 Setup for Changeover Systems Step 12: Tracer UC210 Setup for Changeover Systems Best Practice: Install a duct temperature probe (part number 4190-7020) in the return air duct, before/upstream of the bypass damper. This temperature is used in the changeover application of System Controller to control the VAS AHU member.
  • Page 10: Step 13: System Controller Setup

    Last Name: Display Role: Tracer Concierge or Tracer Concierge without Schedules. In most cases, choose the “Tracer Concierge” role. If you do not want Schedules to appear on the display, choose “Tracer Concierge without Schedules” role. Note: If the system will include a VAV system (VAV, changeover, or changeover bypass) and therefore a VAS, then set the user preference for default priority level to 11 or 8.
  • Page 11: Coordinate Multiple Hvac Units With An Area

    Step 13: System Controller Setup coordinate lights with HVAC or multiple HVAC units together. Areas can also be used to show lighting BOPs on the display. Name areas suitably, as area names are shown on the Tracer Display main screen. Note: Spaces and area names will that are longer than 12 characters will wrap on the main screen.
  • Page 12: Lighting Controlled With Hvac

    Step 13: System Controller Setup Figure 6. Assign lighting member types After creating an area for only lighting members: 1. Click the Configuration tab. 2. Set Unoccupied Heating and Cooling to Disable. Figure 7. Unoccupied operations Important: This will prevent the area from turning on the lights during unoccupied heating and cooling.
  • Page 13 Step 13: System Controller Setup Figure 9. HVAC-only area and HVAC lighting area Changeover Systems Create a Variable Air system 1. Click the Enable Changeover checkbox. 2. Select either Variable Air System or Constant Volume Air System. 3. Enable the optional Optimization functions and click Next. Figure 10.
  • Page 14 DAT point out of service and set it to a value within the limit range so that the system will operate correctly. Schedules • Tracer Concierge only supports System Controller schedules that are type: HVAC and Binary. Analog and multi-state schedules will not appear on the Tracer 10-inch Display.
  • Page 15: Custom Graphics

    Step 13: System Controller Setup Custom Graphics All graphics for Tracer Concierge must be custom graphics. Tracer Concierge will not show standard or template graphics. Order Custom Graphics from Centralized Graphics. On the Graphics Order Sheet, check the Tracer Concierge box, so the graphics are suitable for Tracer 10-inch Display.
  • Page 16: Step 14: Mounting The Display

    • By the optional Wi-Fi router • On the customer network with the System Controller Important: If using the Trane Wi-Fi router, the Tracer 10-inch Display must be powered up after the System Controller and router to ensure the router uses the correct default addresses for System Controller and the display.
  • Page 17: Step 15: Powering The Display

    Step 15: Powering the Display Step 15: Powering the Display 1. Connect the Ethernet cable from System Controller Port 2 to the Tracer 10-inch Display USB Port 1. Or alternatively for a Wi-Fi connection, connect the Ethernet cable from System Controller Port 2 to the Wi-Fi router Port 1. 2.
  • Page 18: Step 16: Display Setup

    3. If connecting to System Controller via the wireless network: a. Choose Wi-Fi and wait for the display to refresh available Wi-Fi networks. b. If using the Wi-Fi router from Trane, select ciscosb1 and verify security is WPA2 PSK. c. Enter the Wi-Fi password: Simple#Retail.
  • Page 19 8. Click Connect. Note: Do not add a port in the IP address field. Tracer Concierge will attempt a secure connection (via https) first. If not available, it will establish a standard connection (http). 9. Select the Zones tab.
  • Page 20 Step 16: Display Setup Figure 18. Options tab 14.Setpoint limit defaults to +/-3 degrees. From the Options tab, you can change the setpoint limit from 1-9 or disable it entirely. Note: This setpoint limit applies to the setpoints on the main screen and will not apply to any custom graphics.
  • Page 21: Step 17: Project Commissioning Checklist

    (level 15), but not as hight as the display (level 13). The override should take affect over the schedule, but the display will be able to control. 2. In Tracer Concierge, tap the power icon to override the area occupied. Verify that the area occupies and that the display dives a 2 hour timer.
  • Page 22: Troubleshooting And Common Questions

    Troubleshooting and Common Questions Troubleshooting and Common Questions Problem Explanation/Resolution Widgets on custom Even though they look similar to the main screen, these widgets do not graphics do not follow the follow the Setpoint limit range set on the Options tab. The limits for the setpoint limit range set on widgets are set within Tracer Graphics Editor widget property dialog.
  • Page 23: Troubleshooting Air-Fi : Wci Does Not Join Network

    Tracer TU. A better channel may be found by trial and error or by using a purchased tool such as WiSpy. Outside of radio range or Relocate WCI or add a repeater too many obstacles Defective WCI Replace See the Tracer Concierge for Small Buildings User Guide (BAS-SVU031) for additional troubleshooting. BAS-SVN208G-EN...
  • Page 24 For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.