Plume Management System; Flue Terminal Positions - Worcester Greenstar 2000 Installation And Maintenance Instructions Manual

Hide thumbs Also See for Greenstar 2000:
Table of Contents

Advertisement

Pre-Installation
4.4.3

Plume management system

NOTICE
Plume management terminal:
▶ The plume management terminal must not be sited within 500mm of
the air intake, and must not exceed the maximum straight length for a
horizontal Ø 60/100mm flue with a 60mm plume management
system.
Horizontal plume management runs
▶ The initial horizontal run from the terminal elbow must have a
minimum 10° fall back, (stop tabs in the elbow prevent less than 10°)
to the appliance for proper disposal of condensate.
▶ Any further horizontal runs after an elbow can be 3°.
WARNING
Minimum plume management length:
The minimum distance of 500mm must be maintained between air inlet
and exhaust.
▶ Do not terminate the plume management inside the terminal
exclusion zone (shaded area) shown in figure 26.
≥140mm
m m
0 0
≥ 5
m
0 m
5 0
m
0 m
5 0
Fig. 26 Terminal exclusion zone
NOTICE
Cutting the 500mm pipe
▶ The Plume management extension kit contains the components
required for such a configuration.
22
100mm
X
5 0
0 m
±80°
m
0010013548-003
Plume management bends
NOTICE
Effective plume management lengths of bends:
Each bend used has an equivalent straight plume management length.
▶ Refer to the table 17.
Bend
Effective plume managnement length
45°
90°
Table 17 Effective length of bends
For every extra 1,000mm of plume management after the first 500mm,
the internal 60/100 flue length must be reduced by 700mm, up to a
maximum of 4,500mm of plume management.
2,800
2,100
1
1,400
[mm]
700
0
500
1,500
Fig. 27 Reduction to flue length as plume length increases graph
[1]
Reduction to flue length [mm] (maximum reduction 2,800mm)
[2]
Plume length [mm] (maximum plume length 4,500mm)
4.4.4

Flue terminal positions

CAUTION
Flue terminal positions
▶ All measurements are the minimum clearances required.
▶ Terminals must be positioned so to avoid combustion products
entering the building.
Greenstar 2000 – 6 721 820 552 (2021/02)
0.75 metres
1.5 metres
2,500
3,500
4,500
2
[mm]
0010023114-001