Electrical Connection - Worcester Greenstar 2000 Installation And Maintenance Instructions Manual

Hide thumbs Also See for Greenstar 2000:
Table of Contents

Advertisement

Installation
Refer to figure 49.
▶ Remove the three inner flue tube retaining screws [1].
– The inner tube will be held in place in the appliance.
▶ Check the appliance flue seal [2] is correctly seated and apply
silicone grease.
Flue turret [A] fitting
▶ Align the flue turret [A] to the appliance flue outlet with flat facing [3]
to the rear of the appliance.
– This should be pushed straight down, on to the appliance.
▶ The three inner flue tube retaining screws [1] are re-used to secure
the flue turret [A].
Vertical adaptor [B] fitting
▶ Align the vertical adaptor [B] to the appliance flue outlet with flat
facing [3] to the rear of the appliance.
– This should be pushed straight down, on to the appliance.
▶ The three replacement retaining screws [4] supplied with the
adaptor kit are used to secure the vertical adaptor [B].
Fig. 49 Flue turret/adaptor connection
40
1
2
A
1
3
B
4
3
0010023595-001
5.5

Electrical connection

DANGER
Risk of electric shock!
▶ Isolate electrical components from the power supply (230 V AC)
(fuse, circuit breaker) and secure against unintentional re-
connection before carrying out any work.
Information on safe isolation can be found in the Health and Safety
Executive guidance HSG85.
▶ Check for zero potential before proceeding with work, using test
equipment approved to GS38 to confirm that the electricity supply is
disconnected.
Electrical considerations:
▶ All electrical work must be carried out by a competent and authorised
person.
▶ All work must comply with the current IET Wiring Regulations.
▶ The isolator shall be situated next to the appliance for new systems
and, where practicable, replacement appliances.
▶ The mains electrical supply to the appliance must be through a fused
double pole isolator.
▶ The isolator must have contact separation of 3mm minimum between
poles. Any system connected to the appliance must not have a
separate electrical supply.
▶ Any additional components that are connected to the appliance that
require 230 Volts must be connected to the same supply as the
appliance.
▶ The correct type of RCD must be employed where additional
protection is required that is suitable for a low energy DC modulating
pump according to IET wiring regulations.
▶ External fuse 3 Amps.
▶ When stripping the wires, ensure copper strands do not fall into the
control box.
NOTICE
Risk of damage from hot appliance components.
Hot appliance components can damage electrical cables.
▶ Ensure all electrical cables are in the correct cable guides and away
from hot appliance components.
Cable routing:
▶ Route cables over the valve bracket avoiding any hot components.
▶ Run power cables separately from signal cables. Interference from
power cables can induce spurious faults on signal cables, ensure that
there is at least 100mm separation between power and signal cables.
▶ Ensure the cables are of sufficient length to allow the control box to
be moved to the service position.
If the power cable is of insufficient length, accessing the connection
terminal ( Fig. 54)
▶ Replace with the following cable types:
– Cable: PVC insulated 0.75 mm
to 90 °C.
– Wiring must comply with the latest edition of BS 7671 (IET wiring
regulations).
▶ Connect the cable so that the protective conductor is longer than the
other wires.
Greenstar 2000 – 6 721 820 552 (2021/02)
2
(24 x 0.2mm) temperature rated

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gr2300iw c

Table of Contents