Pre-Installation
4.3.3

Appliance clearances

• The following details cover the installation, service and maintenance
clearances for the appliance.
CAUTION
Risk of damage to appliance or property
The appliance will overheat if the clearance space around the appliance
is restricted by objects.
▶ Do not restrict this space with the addition of cupboards, shelves etc.
next to or around the appliance.
▶ Do not store any combustible materials on or next to the appliance,
such as clothes, towels, paper or plastic bags.
Fig. 11 Appliance minimum clearances
Minimum clearances
Description
X
Appliance width
Y
Appliance height
Z
Appliance depth
Installation/Maintenance
1
Overall clearance height
2
Overall clearance depth
3
In front of appliance
4
Overall clearance width
5
Above the appliance
6
Either side of appliance
7
Below the appliance
8
Compartment depth
9
Appliance to removable door
1) Side panel height = 710mm
2) Height for either 60/100 flue or 80/125 flue
3) This can be reduced (refer to Reduced front maintenance minimum clearances).
4) Clearance to a combustible material
Table 12 Appliance minimum clearances
18
Reduced front maintenance minimum clearances
The front servicing clearance for this appliance can be reduced to
450mm.
For installations with a front servicing clearance less than 600mm
(minimum of 450mm), the following additional criteria must be
achieved.
• The bottom of the appliance case must be between 1000mm and
1500mm from the floor.
• There must be at least 450mm clearance in front of the appliance to
floor level. Anything sited below the appliance must not protrude into
this clear space.
• There must be at least 200mm clearance to any structure which is
sited below the appliance.
• There must be at least 300mm clear space to either the left hand or
right hand side of the appliance. This clear space must be from the
required clear height above the appliance to floor level.
– This clearance will not apply if the appliance is sited within
Minimum clearances must be observed to any obstruction/ surface,
(dark shaded areas, figures 12 and 13).
Dimensions (mm)
400
1)
724
300
2)
1094/1134
3)
900
3)
600
410
2)
170/210
5
200
4)
320
20
Fig. 12 Reduced front maintenance clearances - Side view
[A]
[1]
[2]
[3]
[4]
300mm of a door way and the door frame is the only obstruction.
1
A
4
Appliance.
Above appliance - Same clearance required as for standard
clearances of 60/100 flue or 80/125mm flue.
In front of appliance - Minimum 450mm.
Bottom of appliance to the floor - 1,000 - 1,500mm.
Below appliance - 200mm
Greenstar 2000 – 6 721 820 552 (2021/02)