Plume Management System; Flue Terminal Positions - Worcester Greenstar 4000 Installation And Maintenance Instructions Manual

Gas-fired condensing combi appliance
Hide thumbs Also See for Greenstar 4000:
Table of Contents

Advertisement

Pre-Installation
4.4.3

Plume management system

The maximum flue length allowed for 0.5m of plume is 9m, each
additional 1m of plume reduces the flue length by 750mm, up to a
maximum of 4.5m of plume management with 6m of flue.
5000
4500
4000
3500
3000
2
2500
[mm]
2000
1500
1000
500
0
0
2000
4000
Fig. 28 Plume length to flue length graph
[1]
Flue length [mm] (maximum 9,000mm with minimum 500mm
plume)
[2]
Plume length [mm] (maximum plume length 4,500mm)
NOTICE
Plume management terminal:
▶ The plume management terminal must not be sited within 500mm of
the air intake, and must not exceed the maximum straight length for a
horizontal Ø 60/100mm flue with a 60mm plume management
system.
Horizontal plume management runs
▶ The initial horizontal run from the terminal elbow must have a
minimum 10° fall back, (stop tabs in the elbow prevent less than 10°)
to the appliance for proper disposal of condensate.
▶ Any further horizontal runs after an elbow can be 3°.
WARNING
Minimum plume management length:
The minimum distance of 500mm must be maintained between air inlet
and exhaust.
▶ Do not terminate the plume management inside the terminal
exclusion zone (shaded area) shown in figure 29.
22
6000
8000
10000
12000
1
[mm]
0010036485-001
≥140mm
m m
0 0
≥ 5
m
0 m
5 0
m
0 m
5 0
Fig. 29 Terminal exclusion zone
NOTICE
Cutting the 500mm pipe
▶ The Plume management extension kit contains the components
required for such a configuration.
Plume management bends
NOTICE
Effective plume management lengths of bends:
Each bend used has an equivalent straight plume management length.
▶ Refer to the table 17.
Bend
Effective plume managnement length
45°
90°
Table 17 Effective length of bends
4.4.4

Flue terminal positions

CAUTION
Flue terminal positions
▶ All measurements are the minimum clearances required.
▶ Terminals must be positioned so to avoid combustion products
entering the building.
Greenstar 4000 – 6 720 891 161 (2020/09)
100mm
X
5 0
0 m
±80°
m
0010013548-003
0.75 metres