Day Occupancy Setting Schedule / Output
Condition programming section, regardless of
modes 01-08.
Follows Schedule / Output Condition only when
Mode is ON. The Day Occupancy Setting will
follow the Schedule / Output Condition only when
a mode assigned to the Day Setting is ON.
See section 9.4 for more information on Schedule/
Output Condition options. See section 8 for more
information on how to program modes.
Option [06]: Night Setting Mode Option
Similar to option [05], only for the Night Occupancy
Setting. See section 9.4 for more information on
Schedule/Output Condition options. See section 8
for more information on how to program modes.
Option [07]: Auxiliary Setting Mode Option
Similar to option [05], only for the Auxiliary
Occupancy Setting. See section 9.4 for more
information on Schedule/Output Condition options.
See section 8 for more information on how to
program modes.
Option [08]: Away Setting Mode Option
Similar to option [05], only for the Away Occupancy
Setting. See section 9.4 for more information on
Schedule/Output Condition options. See section 8
for more information on how to program modes.
9.6 Assigning Schedules for
Temperature Control
There are 16 Automation Schedules in the
VPM5580TC which determine the ON time, OFF
time and Day Mask. See section 7, Automation
Schedule Programming for information on
programming the schedules.
As with Automation items, each of the 4 occupancy
settings (Day, Night, Auxiliary, Away) of each
thermostat can be programmed to automatically
be turned ON by one or more of the schedules in
the VPM5580TC.
Example : If you assign the Day and Night
Occupancy Settings to different schedules, the
VPM5580TC can automatically turn the Day setting
on in the day time and the Night setting on in the
evening.
E
R
A
T
U
firealarmresources.com
R
E
C
O
To program an occupancy setting to follow one or
more schedules, turn ON the options corresponding
to the numbers of the schedules (e.g. turning ON
only option 01, programs the occupancy setting to
follow only schedule number 1).
Do not assign the same schedule to two different
occupancy settings of the same thermostat. For
example, you should not assign schedule (15) to
both the Day Occupancy setting and the Night
Occupancy setting of Thermostat 1.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Schedule Programming .. sections [030] - [077]
Occupancy Setting
Schedule Assignment ..... sections [801] - [879]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
9.7 Assigning Occupancy
Settings to Modes
Mode assignment gives users control over groups of
Automation items or occupancy settings, programmed
for scheduled or event initiated operation. You can
assign any occupancy setting (Day, Night, Auxiliary &
Away) to one or more of 8 modes.
Users can turn modes on or off using the Automation
menu. To have an occupancy setting follow a
mode, turn on the Follows Schedule/Output only
if a Mode is ON option for the occupancy setting
(see section 9.5). Then, assign the occupancy
setting to one or more modes. When the user turns
on one or more modes to which the occupancy
setting is assigned, the occupancy setting will
activate at the scheduled times or when an event
occurs. If all of the modes an occupancy setting is
assigned to are OFF, the setting will not activate
according to schedules/events.
To assign modes, enter the appropriate section
number, and turn options 01 – 08 ON or OFF.
Options 01 – 08 represent modes 1 – 8 respectively.
If the option is ON, automatic control of the selected
occupancy setting for the selected thermostat will
be dependent on that mode (the mode must be
turned ON to enable automatic control). If the
option is OFF, automatic control is not dependent
on that mode.
25
N
T
R
O
L

Advertisement