Powerware 5119 User Manual page 40

1000-3000 va
Table of Contents

Advertisement

Troubleshooting
Alarm or Condition
The Low Battery Alarm
does not give enough
warning.
AC input high
AC input low
Site Wiring Fault
Low Battery Charge
34
Possible Cause
The batteries need charging or
service.
The Low Battery Alarm is not
set appropriately.
The AC input voltage is too
high. The UPS is running on
battery power.
The line voltage is too low. The
UPS is running on battery
power.
Ground wire connection does
not exist in the wall outlet or
the line and neutral wires are
reversed in the wall outlet.
The battery is running low.
Action
Plug the UPS into a wall outlet for 24 hours to charge the
battery. After charging the battery, press and hold the
button for 3 seconds; then check the Battery Service
indicator.
If the Battery Service indicator is still on, see "UPS
Maintenance" on page 19 to replace the battery.
Change the alarm setting. See "Configuration Mode" on
page 15.
Correct the input voltage, if possible. The UPS continues to
operate on battery until the battery is completely discharged.
If the condition persists, the input voltage in your area may
differ from the UPS nominal. Change the UPS input voltage to
match your local voltage (see "Configuration Mode" on
page 15).
Correct the input voltage, if possible. The UPS continues to
operate on battery until the battery is completely discharged.
If the condition persists, the input voltage in your area may
differ from the UPS nominal. Change the UPS input voltage to
match your local voltage (see "Configuration Mode" on
page 15).
Have a qualified electrician correct the wiring.
To disable this alarm, see "Configuration Mode" on page 15.
3 to 5 minutes or less of battery power remains (depending on
load and battery charge).
Prepare for a shutdown. Save your work and turn off your
equipment.
Powerware
5119 User's Guide
®
:
www.powerware.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents