Pin Out - Powerware 5119 User Manual

1000-3000 va
Table of Contents

Advertisement

Additional UPS Features

Pin Out

As shown in Table 2, Pins 1 and 2 operate in two modes: Basic Alarms
mode and Serial Data mode. Basic Alarms mode has AC fail alarm and
output shutdown. Serial Data mode is UPS Code II compliant.
The system always starts in Basic Alarms mode. When serial data is
received at Pin 1, the function of Pin 1 and Pin 2 changes to Serial Data
mode.
If serial data has not been received before going to battery power, serial
communication is disabled until AC input power returns.
Table 2. Communication Port Configuration
Pin
Signal Type
1
Basic Alarms Mode - Input: RS-232 level high (+12V) pulse
4 to 5 seconds
Serial Data Mode - Input: RS-232 data
2
Basic Alarms Mode - Output: RS-232 level high (+12V)
Serial Data Mode - Output: RS-232 data
3
Output: Open collector transistor ON, 50 mA, 40 Vdc rating
4
Signal Common
5
Output: Open collector transistor ON, 50 mA, 40 Vdc rating
6
Input: RS-232 RTS
7
Input: Relay contact or RS-232 level
8
Output: 8 to 25 Vdc, 5W constant power (0.63A max. @ 8V)
9
Chassis
26
6 7 8 9
1 2 3 4 5
Figure 17. Communication Port
Function
Remote UPS off. In absence of AC power, output is
turned off until normal AC power returns
RS-232 serial communication input. 1200 baud,
8 bits, No parity, 1 stop bit, 1 start bit
AC Input failure
RS-232 serial communication output. 1200 baud,
8 bits, No parity, 1 stop bit, 1 start bit
AC Input failure
Signal Common
Impending low battery
Plug-and-play software enable trigger (activates
when pin changes from +12V to -12V)
Remote Emergency Power-Off: UPS total output can
be kept off with low signal or closing relay contact
Auxiliary Control Power
Connection to chassis
Powerware
5119 User's Guide
®
:
www.powerware.com