Table 7. Environmental and Safety
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Audible Noise
Surge Suppression
Safety Conformance
Safety Markings
EMC
Table 8. Indicators and Controls
Serial Communication
Interface
Contact Closures
Table 9. Battery
Configuration
Voltage
Type
Charging
Monitoring
Powerware
5119 User's Guide
®
120V Models
0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
UL 1778; CAN/CSA C22.2, No. 107.1
UL, CSA
FCC, VCCI
Intelligent serial communication to provide alarms with history, measured parameters, self-test,
and many other features; contact your authorized dealer for UPS/computer communication
software options
Ergonomic Indicators: Wiring Fault, Battery Service, Communication, Operation, System Normal
Bar Graphs: Input Level, Battery Charge Level, % Load
AC Input Failure, Low Battery
120V Models
1000-1500 VA: internal batteries
2000-3000 VA: external PW5119 1048BP
24 Vdc for internal; 48 Vdc for external
Sealed, maintenance-free, valve-regulated, lead-acid
Advanced charging for faster recovery; approximately 4 hours to 90% usable capacity at nominal
line and no supplementary power supply load
Advanced monitoring for earlier failure detection and warning
:
www.powerware.com
-20°C to 60°C (-4°F to 140°F)
5-95% noncondensing
Up to 3,000 meters above sea level
Less than 45 dBA typical
IEEE 587/ANSI C62.41 Category B
UL 1778; CAN/CSA C22.2, No. 107.1;
1000-1500 VA: internal batteries
2000-3000 VA: external PW5119 1748BP
Specifications
230V Models
EN 50091-1 and IEC 60950
UL, CSA, CE
EN 50091-2
230V Models
31