14 Parameter list
Number
Parameter Description
P17
Set value
Upper
limit OPEN
range of
the set
value limit
P18
Close tight
Lower
function
range of
CLOSED
the close
tight func-
tion
P19
Close tight
Upper
function
range of
OPEN
the close
tight func-
tion
P01
Split range
Starting
start
point of the
split-range
function
P02
Split range
End point
end
of the split-
range func-
tion
P15
Set value
Inversion
direction of
of the tar-
action
get value
signal
P14
Control
The control
curve
curve is
defined
P03
Character-
Calibration
istic curve
point 0 of
point 0%
the free
character-
istic
P04
Character-
Calibration
istic curve
point 10 of
point 10%
the free
character-
istic
P05
Character-
Calibration
istic curve
point 20 of
point 20%
the free
character-
istic
P06
Character-
Calibration
istic curve
point 30 of
point 30%
the free
character-
istic
P07
Character-
Calibration
istic curve
point 40 of
point 40%
the free
character-
istic
GEMÜ 1441 cPos-X
Settings
Initial set-
ting
0 to 100%
0%
0.0 to
0.5%
20.0%
80.0 to
99.5%
100.0%
0.0 to
0.0%
90.0%
10.0 to
100.0%
100.0%
rise, fall
rise
Linear,
Linear
1:25, 1:50,
free
0.0 to
0.0%
100.0%
0.0 to
10.0%
100.0%
0.0 to
20.0%
100.0%
0.0 to
30.0%
100.0%
0.0 to
40.0%
100.0%
26 / 33
Number
Parameter Description
P08
Character-
Calibration
istic curve
point 50 of
point 50%
the free
character-
istic
P09
Character-
Calibration
istic curve
point 60 of
point 60%
the free
character-
istic
P10
Character-
Calibration
istic curve
point 70 of
point 70%
the free
character-
istic
P11
Character-
Calibration
istic curve
point 80 of
point 80%
the free
character-
istic
P12
Character-
Calibration
istic curve
point 90 of
point 90%
the free
character-
istic
P13
Character-
Calibration
istic curve
point 100
point 100%
of the free
character-
istic
P36
Error posi-
Valve posi-
tion
tion at er-
ror mes-
sage
P27
Control
Control
function
function of
the pro-
cess valve
P37
Error time
Debounce
time of er-
ror mes-
sages
P38
Set value I
Switch-off
min
limit for
cable break
recognition
of the set
value
P39
Set value I
Switch-off
max
limit for ex-
cess cur-
rent recog-
nition of
the set
value
Settings
Initial set-
ting
0.0 to
50.0%
100.0%
0.0 to
60.0%
100.0%
0.0 to
70.0%
100.0%
0.0 to
80.0%
100.0%
0.0 to
90.0%
100.0%
0.0 to
100.0%
100.0%
Close,
Close
Open, Hold,
Safe
0.2 to
0.2 s
100.0 s
0.0 to 22.0
3.5 mA
mA
0.0 to 22.0
20.5 mA
mA