4.5

Programming

4.5.1

Programming of Individual Address (and Application)

The Individual Address (IA) can be assigned to MECip-Sec by setting the desired address in
the properties window of ETS. After downloading it into the device, MECip-Sec can be
addressed and identified by its new Individual Address.
To download the Individual Address into the device, Programming Mode must be active.
Successive pressing the Programming Button switches Programming Mode on and off. LED 7
lighting red indicates Programming Mode is on. Once the download is started in ETS, the
Programming Button has to be pressed. After that, the new Individual Address becomes
stored in the memory of the device.
To program devices of a line different to which the device used as ETS Current Interface
is connected, a correct topology is mandatory.
The device is supplied with the Individual Address 15.15.0 (Factory Default Setting). It is
recommended not to use this address for normal operation and to assign a different
address when commissioning.
A blinking red Programming LED indicates the Ethernet cable is not properly connected
or no IP network connection is available.
Operational Description
Figure 9: ETS Properties Window
MECip
SECURE