Indoor Fan Motor Or Related Abnormality - Daikin MKS-T Series Service Manual

Table of Contents

Advertisement

Troubleshooting for Wall Mounted and LSP Duct Type Indoor Unit
5.3

Indoor Fan Motor or Related Abnormality

5.3.1 DC Fan Motor or Related Abnormality
Applicable
CTKS25/35/50/60/71TVMG
CTKB25/35/50/60TVMG
Models
A6
Error Code
Method of Error
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Detection
Error Decision
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
Conditions
is less than 50% of the maximum fan motor rotation speed.
Supposed
 Remarkable decrease in power supply voltage
Causes
 Layer short inside the fan motor winding
 Breaking of wire inside the fan motor
 Breaking of the fan motor lead wires
 Defective capacitor of the fan motor
 Defective indoor unit PCB
Troubleshooting
119
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power supply.
(Unplug the power cable or turn
the breaker off.)
Check the connector for
connection.
OK?
YES
Foreign matters in or
around the fan?
NO
Rotate the fan by hand.
A
Go to the next page
Note: The motor may break when the
motor connector is disconnected
with the power supply on.
(Turn off the power supply before
connecting the connector also.)
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
NO
YES
SiSG121917E
Correct the connection.
Remove the foreign matters.
(R23939)