Daikin MKS-T Series Service Manual page 193

Table of Contents

Advertisement

SiSG121917E
 With ARC433 Series Remote Controller
1. Press ON/OFF button to turn on the system.
2. Press the center of TEMP button and MODE button at the same time.
3. Press MODE button twice.
4. Press MODE button and select operation mode.
5. Trial operation terminates in about 30 minutes and switches into normal mode.
 With BRC086A22 Remote Controller
1. Completely open the stop valve on gas side.
2. Completely open the stop valve on liquid side.
3. Set to cooling or heating operation using the remote controller, and then start the operation
4. Press INSPECTION button 2 times, and let the operation continue for 3 minutes in the test
5. Press INSPECTION button 1 time to return to normal operation mode.
6. Check the functions in accordance with operation manual.
Part 7 Trial Operation and Field Settings
(T appears on the display to indicate that trial operation is selected.)
To quit a trial operation, press ON/OFF button.
2, 3, 4
by pressing ON/OFF button.
operation mode.
4, 5
Trial Operation
3
2
1, 5
(R16394)
3
(R24947)
188