Daikin MKS-T Series Service Manual page 197

Table of Contents

Advertisement

SiSG121917E
LSP Duct Type
1. Cut the jumper JA on indoor unit control PCB.
2. Remove the battery cover of the remote controller and cut the address jumper (J4).
Indoor Unit
Wireless Remote Controller
1. Remove the cover.
2. Cut the address setting jumper.
Caution
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Caution
Replace the remote controller if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
5.1.2 Jumper and Switch Settings
Fan speed setting
when compressor
stops for
thermostat OFF.
(effective only at
cooling operation)
Power failure
recovery function
Reference
For the location of the jumpers, refer to the following pages.
FDKS Series: page 32
Part 7 Trial Operation and Field Settings
JA
JB
ADDRESS
JC
ADDRESS
EXIST
CUT
Jumper (on indoor
Function
unit PCB)
JB
JC
ADDRESS : JA
EXIST
1
CUT
2
1
2
When connected
(factory setting)
Fan speed setting ;
Remote controller
setting
Auto-restart
Field Settings
1
2
3
(R22633)
Jumper
(R6573)
When cut
The fan stops.
The unit does not resume
operation after recovering
from a power failure. Timer
settings are cleared.
192