5.3
Indoor Fan Motor or Related Abnormality
5.3.1 Indoor Fan Motor (DC Motor) or Related Abnormality
Applicable
FTXR09/12/18TVJUW(S)
Models
CTXG09/12/18QVJUW(S)
CTXS07LVJU
FTXS09/12/15/18/24LVJU
FVXS09/12/15/18NVJU
A6
Error Code
Method of Error
The rotation speed detected by the Hall IC during indoor fan motor operation determines abnormal
Detection
fan motor operation.
Error Decision
The detected rotation speed does not reach the demanded rotation speed of the target tap, and is
Conditions
less than 50% of the maximum fan motor rotation speed.
Supposed
Remarkable decrease in power supply voltage
Causes
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB