Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
G. NORMAL RUN WITH OVERRIDES
PRIMARY
STATE
MESSAGE
120
RUN CAPACITY
LIMITED
121
RUN CAPACITY
LIMITED
122
RUN CAPACITY
LIMITED
123
RUN CAPACITY
LIMITED
124
RUN CAPACITY
LIMITED
125
RUN CAPACITY
LIMITED
*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,
alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control has recorded at the time of the fault con-
dition.
H. OUT-OF-RANGE SENSOR ALARMS
PRIMARY
STATE
MESSAGE
260
SENSOR
LEAVING CHILLED
FAULT
WATER
261
SENSOR
ENTERING CHILLED
FAULT
WATER
262
SENSOR
CONDENSER
FAULT
PRESSURE
263
SENSOR
EVAPORATOR
FAULT
PRESSURE
264
SENSOR
COMPRESSOR
FAULT
BEARING TEMP
265
SENSOR
COMPRESSOR
FAULT
MOTOR TEMP
266
SENSOR
COMP DISCHARGE
FAULT
TEMP
267
SENSOR
OIL SUMP TEMP
FAULT
268
SENSOR
COMP OIL
FAULT
PRESS DIFF
269
SENSOR
CHILLED WATER
FAULT
FLOW
270
SENSOR
COND WATER
FAULT
FLOW
271
SENSOR
VFD SPEED SENSOR
FAULT
OUT OF RANGE
273
SENSOR
VFD SPEED OUT OF
FAULT
RANGE
Table 11 — CVC/ICVC Primary and Secondary Messages and
SECONDARY
MESSAGE
HIGH CONDENSER
120->Condenser Pressure
PRESSURE
[VALUE] exceeded limit of [LIMIT]*.
HIGH MOTOR
121->Comp Motor Winding Temp
TEMPERATURE
[VALUE] exceeded limit of [LIMIT]*.
LOW EVAP
122->Evaporator Refrig Temp
REFRIG TEMP
[VALUE] exceeded limit of [LIMIT]*.
HIGH COMPRESSOR
123->Surge Prevention Override:
LIFT
Lift Too High For Compressor.
MANUAL GUIDE
124->Run Capacity Limited:
VANE TARGET
Manual Guide Vane Target.
LOW DISCHARGE
No messages.
SUPERHEAT
SECONDARY
MESSAGE
260->Sensor Fault:
Leaving Chilled Water
261->Sensor Fault:
Entering Chilled Water
262->Sensor Fault:
Condenser Pressure
263->Sensor Fault:
Evaporator Pressure
264->Sensor Fault:
Comp Thrust Bearing Temp
265->Sensor Fault:
Comp Motor Winding Temp
266->Sensor Fault:
Comp Discharge Temp
267->Sensor Fault:
Oil Sump Temp
268->Sensor Fault:
Oil Pump Delta P
269->Sensor Fault:
Chilled Water Delta P
270->Sensor Fault:
Cond Water Delta P
271->Sensor Fault:
Check Actual VFD Speed Sensor
273->Sensor Fault:
Check Actual VFD Speed Sensor
ALARM MESSAGE
PRIMARY CAUSE
Check for high condenser water temperatures.
Check setting in SETUP1.
Check motor cooling lines.
Check for closed valves.
Check setting in SETUP1.
Check refrigerant charge.
Check for low entering cooler temperatures.
Check for high condenser water temperatures or
low suction temperature.
Target guide vane point has been forced in
MAINSTAT screen. Release force to continue
normal operation.
Check oil charge.
Check refrigerant charge.
ALARM MESSAGE
PRIMARY CAUSE
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor wiring.
Check sensor wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor wiring and accuracy.
Check sensor wiring and accuracy.
Check sensor wiring and accuracy.
Check voltage input on terminals J6-1 and J6-2 on
the ISM module. Check wiring.
Check VFD feedback 0-5 vac. Calibrate VFD
speed reference signal.
80
ADDITIONAL
CAUSE/REMEDY
ADDITIONAL
CAUSE/REMEDY