Carrier 19XR User Manual page 79

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Table of Contents

Advertisement

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
PRIMARY
STATE
MESSAGE
100
PRESTART
STARTS LIMIT
ALERT
EXCEEDED
101
PRESTART
HIGH BEARING
ALERT
TEMPERATURE
102
PRESTART
HIGH MOTOR
ALERT
TEMPERATURE
103
PRESTART
HIGH DISCHARGE
ALERT
TEMP
104
PRESTART
LOW REFRIGERANT
ALERT
TEMP
105
PRESTART
LOW OIL
ALERT
TEMPERATURE
106
PRESTART
HIGH CONDENSER
ALERT
PRESSURE
107
PRESTART
LOW LINE
ALERT
VOLTAGE
108
PRESTART
HIGH LINE
ALERT
VOLTAGE
109
PRESTART
GUIDE VANE
ALERT
CALIBRATION
*[LIMIT] is shown on the CVC/ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert.
[VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
E. START-UP IN PROGRESS
PRIMARY MESSAGE
STARTUP IN PROGRESS
STARTUP IN PROGRESS
STARTUP IN PROGRESS
AUTORESTART IN PROGRESS
AUTORESTART IN PROGRESS
AUTORESTART IN PROGRESS
F. NORMAL RUN
PRIMARY MESSAGE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING —TEMP CONTROL
Table 11 — CVC/ICVC Primary and Secondary Messages and
SECONDARY
ALARM MESSAGE
MESSAGE
100->Excessive compressor
starts (8 in 12 hours)
101->Comp Thrust Bearing
Temp [VALUE] exceeded
limit of [LIMIT]*.
102->Comp Motor Winding Temp
[VALUE] exceeded limit
of [LIMIT]*.
103->Comp Discharge Temp
[VALUE] exceeded limit of
[LIMIT]*.
104->Evaporator Refrig Temp
[VALUE] exceeded limit of
[LIMIT]*.
105->Oil Sump Temp [VALUE]
exceeded limit of [LIMIT]*.
106->Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
107->Average Line Voltage
[VALUE] exceeded limit of
[LIMIT]*.
108->Average Line Voltage
[VALUE] exceeded limit of
[LIMIT]*.
109->Actual Guide Vane
Pos Calibration Required
Before Start-Up
SECONDARY MESSAGE
OCCUPIED MODE
REMOTE CONTACT CLOSED
START COMMAND IN EFFECT
OCCUPIED MODE
REMOTE CONTACT CLOSED
START COMMAND IN EFFECT
SECONDARY MESSAGE
4-20 mA SIGNAL
REMOTE TEMP SENSOR
CHW TEMP DIFFERENCE
LEAVING CHILLED WATER
ENTERING CHILLED WATER
TEMPERATURE RAMP LOADING
BY DEMAND RAMP LOADING
BY LOCAL DEMAND SETPOINT
BY 4-20 mA SIGNAL
BY CCN SIGNAL
BY LOADSHED/REDLINE
HOT GAS BYPASS
BY LOCAL SIGNAL
ICE BUILD MODE
PRIMARY CAUSE
Depress the RESET softkey if additional start is
required. Reassess start-up requirements.
Check oil heater for proper operation.
Check for low oil level, partially closed coil supply
valves, clogged oil filters, etc.
Check the sensor wiring and accuracy.
Check configurable range in SETUP1 screen.
Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation, or
restrictions.
Check for excessive starts within a short time span.
Check configurable range in SETUP1 screen.
Allow discharge sensor to cool.
Check for sensor wiring and accuracy.
Check for excessive starts.
Check configurable range in SETUP1 screen.
Check transducer wiring and accuracy.
Check for low chilled fluid supply temperatures.
Check refrigerant charge.
Check oil heater contactor/relay and power.
Check oil level and oil pump operation.
Check transducer wiring and accuracy.
Check for high condenser water temperatures.
Check voltage supply. Check voltage transformers.
Consult power utility if voltage is low.
Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.
Calibrate guide vane actuator in Control Test.
CAUSE/REMEDY
Chiller is starting. Time schedule is occupied.
Chiller is starting. Remote contacts are enabled and closed.
Chiller is starting. Chiller START/STOP in MAINSTAT manually forced to
start.
Chiller is starting after power failure. Time schedule is occupied.
Chiller is starting after power failure. Remote contacts are enabled and
closed.
Chiller is starting after power failure. Chiller START/STOP on MAINSTAT
manually forced to start.
CAUSE/REMEDY
Auto chilled water reset active based on external input.
Auto chilled water reset active based on external input.
Auto chilled water reset active based on cooler ∆T.
Default method of temperature control.
Entering Chilled Water (ECW) control enabled in TEMP_CTL screen
Ramp Loading in effect. Use RAMP_DEM screen to modify.
Ramp Loading in effect. Use RAMP_DEM screen to modify.
Demand limit set point is less than actual demand.
Demand limit is active based on external auto demand limit option.
Demand limit is active based on control limit signal from CCN.
Demand limit is active based on LOADSHED screen set-up.
Hot gas bypass option is energized. See stall prevention in the control
section.
Active demand limit manually overridden on MAINSTAT table.
Chiller is running under Ice Build temperature control.
79
ADDITIONAL CAUSE/REMEDY