General —
The 19XR hermetic centrifugal liquid chiller
contains a microprocessor-based control center that monitors
and controls all operations of the chiller (see Fig. 9). The
microprocessor control system matches the cooling capacity of
the chiller to the cooling load while providing state-of-the-art
chiller protection. The system controls cooling load within the
set point plus the deadband by sensing the leaving chilled water
or brine temperature and regulating the inlet guide vane via a
mechanically linked actuator motor. The guide vane is a vari-
able flow pre-whirl assembly that controls the refrigeration ef-
fect in the cooler by regulating the amount of refrigerant vapor
flow into the compressor. An increase in guide vane opening
increases capacity. A decrease in guide vane opening decreases
capacity. The microprocessor-based control center protects the
chiller by monitoring the digital and analog inputs and execut-
ing capacity overrides or safety shutdowns, if required.
Fig. 7 — Variable Frequency Drive (VFD)
LINE
LOAD
Fig. 8 — Variable Frequency Drive (VFD) Starter Internal View
Forward
AUTO
SPEED
RUNNING
MAN
Reverse
VOLTS
REMOTE
AMPS
JOG
PRO-
RUN
Hz
AUTO
GRAM
JOB
Kw
FORWARD
TORQUE
REVERSE
ENTER
Password
PROGRAM
RUNNING
SPEED
VOLTS
REMOTE
AMPS
Hz
Kw
FORWARD
TORQUE
REVERSE
Password
PROGRAM
TXV
PIC II System Components —
system is called the PIC II (Product Integrated Control II). See
Table 1. The PIC II controls the operation of the chiller by
monitoring all operating conditions. The PIC II can diagnose a
problem and let the operator know what the problem is and
what to check. It promptly positions the guide vanes to main-
tain leaving chilled water temperature. It can interface with
auxiliary equipment such as pumps and cooling tower fans to
turn them on when required. It continually checks all safeties to
prevent any unsafe operating condition. It also regulates the oil
heater while the compressor is off and regulates the hot gas by-
pass valve, if installed. The PIC II controls provide critical pro-
tection for the compressor motor and controls the motor starter.
11
Forward
AUTO
RUNNING
SPEED
MAN
Reverse
VOLTS
REMOTE
RUN
AMPS
JOG
PROGRAM
Hz
AUTO
JOB
FORWARD
Kw
TORQUE
REVERSE
ENTER
PROGRAM
Password
MANUAL RESET
+
DC BUS BAR
MEASUREMENT
-
POINT
INITIAL DC BUS
MEASUREMENT
POINT
+
DANGER
HIGH VOLTAGE
AUTO
Forward
MAN
Reverse
JOG
RUN
PROGRAM
AUTO
JOB
ENTER
VFD
MODULE
COOLING LINES
The chiller control
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xrv19xrv

Table of Contents