DESCRIPTION
Comp Motor Temp Override
Cond Press Override
Comp Discharge Alert
Comp Thrust Brg Alert
Chilled Medium
Chilled Water Deadband
Evap Refrig Trippoint
Refrig Override Delta T
Condenser Freeze Point
Evap Flow Delta P Cutout
Cond Flow Delta P Cutout
Water Flow Verify Time
Oil Press Verify Time
Recycle Control
Restart Delta T
Shutdown Delta T
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
Spare Temp #1 Limit
Spare Temp #2 Enable
Spare Temp #2 Limit
19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET
RANGE
150 to 200
90 to 165
125 to 200
165 to 185
0/1
.5 to 2.0
0.0 to 40.0
2.0 to 5.0
–20 to 35
0.5 to 50.0
0.5 to 50.0
0.5 to 5
15 to 300
2.0 to 10.0
0.5 to 4.0
0 to 4
–40 to 245
0 to 4
–40 to 245
UNITS
DEG F
200
PSI
125
DEG F
200
DEG F
175
WATER/BRINE
WATER
ˆF
1.0
DEG F
33
ˆF
3
DEG F
34
PSI
5.0
PSI
5.0
MIN
5
SEC
40
DEG F
5
DEG F
1
0
DEG F
245
0
DEG F
245
CL-7
DEFAULT
VALUE