the CONTROL TEST table to turn on the water
pumps and monitor pressures.
If the chilled water and condenser water pumps are not
controlled by the PIC II, these pumps must be started and
stopped manually at the appropriate times during the refrig-
erant transfer procedure.
b. Close pumpout unit valves 2, 4, 5, 8, and 10, and
close chiller charging valve 7; open chiller isola-
tion valves 11, 12, 13, and 14 (if present).
c. Open pumpout unit/storage tank valves 3 and 6,
open chiller valves 1a and 1b.
VALVE
1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
C
C C
C C C
CONDITION
Follow Steps d and e carefully to prevent damage from
freeze-up.
d. Slowly open valve 5 to increase chiller pressure to
68 psig 35 psig (141 kPa) for HFC-134a. Feed
refrigerant slowly to prevent freeze up.
e. Open valve 5 fully after the pressure rises above
the freeze point of the refrigerant. Open liquid line
valves 7 and 10 until refrigerant pressure
equalizes.
VALVE
1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
C
C
C
CONDITION
2. Transfer the remaining refrigerant.
a. Close valve 5 and open valve 4.
VALVE
1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
C
C
C
CONDITION
b. Turn off the chiller water pumps using the CVC/
ICVC (or manually, if necessary).
c. Turn off the pumpout condenser water, and turn on
the pumpout compressor to push liquid out of the
storage tank.
d. Close liquid line valve 7.
e. Turn off the pumpout compressor.
f. Close valves 3 and 4.
g. Open valves 2 and 5.
VALVE
1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
C C
C C
CONDITION
h. Turn on the pumpout condenser water.
i. Run the pumpout compressor until the pumpout
storage tank pressure reaches 5 psig (34 kPa)
(18 in. Hg [40 kPa absolute] if repairing the tank).
j. Turn off the pumpout compressor.
k. Close valves 1a, 1b, 2, 5, 6, and 10.
VALVE
1a 1b 2 3 4 5 6 7 8 10 11 12 13 14
CONDITION C C C C C C C C C C
l. Turn off pumpout condenser water.
Page 69