NOTE: Because a schedule is integral to the chiller control
sequence, the chiller will not start until the time and date have
been set.
CHANGE CVC/ICVC CONFIGURATION IF NECES-
SARY — From the SERVICE table, access the CVC/ICVC
CONFIGU-RATION screen. From there, view or modify the
CVC/ICVC CCN address, change to English or SI units, and
change the password. If there is more than one chiller at the
jobsite, change the CVC/ICVC address on each chiller so that
each chiller has its own address. Note and record the new
address. Change the screen to SI units as required, and change
the password if desired.
TO CHANGE THE PASSWORD — The password may be
changed from the CVC/ICVC CONFIGURATION screen.
1. Press the
and
MENU
current password and highlight CVC/ICVC CONFIGU-
RATION. Press the
SELECT
5 entries on the CVC/ICVC CONFIG screen can be
changed: BUS #, ADDRESS #, BAUD RATE, US IMP/
METRIC, and PASSWORD.
2. Use the
softkey to scroll to PASSWORD. The
ENTER
first digit of the password is highlighted on the screen.
3. To change the digit, press the
softkey. When the desired digit is seen,
DECREASE
press the
softkey.
ENTER
4. The next digit is highlighted. Change it, and the third and
fourth digits in the same way the first was changed.
5. After the last digit is changed, the CVC/ICVC goes to the
BUS parameter. Press the
screen and return to the SERVICE menu.
Be sure to remember the password. Retain a copy
for future reference. Without the password, access to the
SERVICE menu will not be possible unless the CVC/
ICVC_PSWD menu on the STATUS screen is accessed by
a Carrier representative.
TO CHANGE THE CVC/ICVC DISPLAY FROM
ENGLISH TO METRIC UNITS — By default, the CVC/
ICVC displays information in English units. To change to met-
ric units, access the CVC/ICVC CONFIGURATION screen:
1. Press the
and
MENU
password and highlight CVC/ICVC CONFIGURATION.
Press the
softkey.
SELECT
2. Use the
softkey to scroll to US IMP/METRIC.
ENTER
3. Press the softkey that corresponds to the units desired for
display on the CVC/ICVC (e.g., US or METRIC).
CHANGE LANGUAGE (ICVC Only) — By default, the
ICVC displays information in English. To change to another
Language, access the ICVC CONFIGURATION screen:
1. Press the
and
MENU
password and highlight ICVC CONFIGURATION. Press
the
softkey.
SELECT
2. Use the
softkey to scroll to LID LANGUAGE.
ENTER
3. Press the INCREASE or DECREASE softkey until the
desired language is displayed. Press
desired language.
MODIFY CONTROLLER IDENTIFICATION IF NECES-
SARY — The CVC/ICVC module address can be changed
from the CVC/ICVC CONFIGURATION screen. Change this
softkeys. Enter the
SERVICE
softkey. Only the last
INCREASE
softkey to leave that
EXIT
softkeys. Enter the
SERVICE
softkeys. Enter the
SERVICE
to confirm
ENTER
address for each chiller if there is more than one chiller at the
jobsite. Write the new address on the CVC/ICVC module for
future reference.
INPUT EQUIPMENT SERVICE PARAMETERS IF NEC-
ESSARY — The EQUIPMENT SERVICE table has six
service tables.
Configure SERVICE Tables — Access the SERVICE tables,
shown in Table 2, to modify or view job site parameters:
PARAMETER
Starter Type
Motor Rated Line
Voltage
Volt Transformer
Ratio
Motor Rated
Load Amps
Motor Locked
Rotor Trip
Starter LRA
Rating
or
Motor Current
CT Ratio
Ground Fault
Current
Transformers
Ground Fault
CT Ratio
Single Cycle
Dropout
Line Frequency
Line Frequency
Faulting
Surge Limiting or
Hot Gas Bypass
Option
Minimum Load
Points (T1, P1)
Full (Maximum)
Load Points (T2, P2)
Chilled Medium
Evaporator
Refrigerant
Trippoint
Evaporator Flow
Delta P Cutout
Condenser Flow
Delta P Cutout
Diffuser Option
(Compressors with Split
Ring Diffusers)
Diffuser Full Span
mA Rating
(Compressors with Split
Ring Diffusers)
Motor Rated
Kilowatts
*With variable flow systems this point may be configured to the lower end of
the range.
NOTE: Other parameters: Screens are normally left at the default settings; they
may be changed by the operator as required. The time and persistence set-
tings on the ISM_CONF table can be adjusted to increase or decrease the sen-
sitivity to a fault condition. Increasing time or persistence decreases sensitivity.
Decreasing time or persistence increases sensitivity to the fault condition.
56
TABLE
ISM_CONF — Select 0 for full voltage, 1 for
reduced voltage, or 2 for solid state/variable fre-
quency drive.
ISM_CONF — Motor rated voltage from chiller
information nameplate.
ISM_CONF — Enter ratio (reduced to a ratio to
1) of power transformer wired to terminal J3 of
ISM. If no transformer is used enter 1.
ISM_CONF — Per chiller identification name-
plate data.
ISM_CONF — Per chiller identification name-
plate data. Enter locked rotor delta amps (LR
AMPS D-).
ISM_CONF — Enter value from nameplate in
starter cabinet
Allen -Bradley this appears as "max locked rotor
current @100% nom. voltage."
Benshaw Starters: value is entered as 9999.
ISM_CONF — Enter ratio (reduced to a ratio to
1) of current transformers wired to terminal J4 of
ISM. For Benshaw Inc. RediStart MICRO™
Starters set to 100.
ISM_CONF — Enter 0 if no ground fault CTs are
wired to terminal J5 of ISM. Enter 1 if ground
fault CTs are used.
ISM_CONF — Enter ratio (reduced to a ratio to
1) of ground fault CT.
ISM_CONF — ENABLE if motor protection
required from drop in line voltage within one
cycle.
ISM_CONF — Enter YES for 60 Hz or NO for 50
Hz.
ISM_CONF — ENABLE if motor
protection required for drop in line
frequency.
OPTIONS — Enter 1 if HGBP is installed.
OPTIONS — Per Chiller Requisition (DT1, DP2)
if available or per job data — See modify load
points section.
OPTIONS — Per Chiller Requisition (DT2, DP2)
if available or per job data — See modify load
points section. For VFD units refer to table
located in control panel.
SETUP1 — Enter water or brine.
SETUP1 — Usually 3° F (1.7° C) below design
refrigerant temperature.
SETUP1 — Per Chiller Requisition if available or
enter 50% of design pressure drop to 0.5 psi (3.4
kPa).*
SETUP1 — Per Chiller Requisition if available or
enter 50% of design pressure drop to 0.5 psi (3.4
kPa).*
SETUP2 — ENABLE for 4 and 5 size compres-
sor. See model number nomenclature.
SETUP2 — Enter diffuser actuator full span mA
rating for 4 and 5 size compressor. Value is
located on label on side of diffuser actuator
motor.
RAMP_DEM — Enter value from chiller requisi-
tion form (product data submittal) if kilowatt ramp
demand is enabled.