DESCRIPTION
Auto Restart Option
Remote Contacts Option
Soft Stop Amps Threshold
Surge/Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Min. Load Point (T1, P1)
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Full Load Point (T2, P2)
Surge/HGBP Delta T2
Surge/HGBP Delta P2
Surge/HGBP Deadband
Surge Protection
Surge Delta% Amps
Surge Time Period
Ice Build Control
Ice Build Option
Ice Build Termination
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle
Refrigerant Leak Option
Refrigerant Leak Alarm mA
Head Pressure Reference
Delta P at 0% (4 mA)
Delta P at 100% (20 mA)
Minimum Output
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET
RANGE
0/1
0/1
40 to 100
0/1
0.5 to 20
30 to 170
0.5 to 20
50 to 170
0.5 to 3
5 to 20
7 to 10
0/1
0 to 2
0/1
0/1
4 to 20
20 to 60
20 to 60
0 to 100
UNITS
DSABLE/ENABLE
DSABLE/ENABLE
%
ˆF
PSI
ˆF
PSI
ˆF
%
MIN
DSABLE/ENABLE
DSABLE/ENABLE
DSABLE/ENABLE
mA
psi
psi
%
CL-6
DEFAULT
VALUE
DSABLE
DSABLE
100
0
1.5
50
10
85
1
10
8
DSABLE
0
DSABLE
DSABLE
20
25
35
0