Appendix 1 Specifications - YASKAWA CIMR-SSA Series Instruction Manual

Table of Contents

Advertisement

APPENDIX 1
Model
Mounting Method
Enclosure
Rated min
Output Range
Output Range
Speed Control Range (Continuous)
Time Rating
Insulation Class
Sensor
Input Voltage
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Control Method
Starting Torque
Speed Control Range
Speed Control Accuracy
Torque Limit
Torque Accuracy
Run Speed Resolution
Run Speed Resolution
Overload Capacity
Run Speed Setting Signal
Accel/decel Time
Main Functions
Motor Overload Protection
Instantaneous Overcurrent
Blown Fuse Protection
Overload
Overvoltage
Undervoltage
Heatsink Overheat
Stall Prevention
(Overvoltage Prevention)
Ground Fault
Power Charge Indication
Location
Humidity
Storage Temperature
Ambient Temperature
Elevation
Vibration
72
SPECIFICATIONS
Table A−1 Variable Torque Series Specifications
-1
200V class
400V class
200V class: Motor coasts to a stop if main-circuit voltage drops to 190V or below.
400V class: Motor coasts to a stop if main-circuit voltage drops to 380V or below.
-10°C to +40°C (Enclosed wall-mounted type), -10°C to +45°C (Open chassis type)
*Constant output range is as follows:
-1
1750 min
1:1.5 (0.4 to 75 kW)
1:1.3 (90 to 160 kW)
Note: Variable torque series cannot be used to the following applications:
• Commercial power supply / inverter power supply switch operation
• One inverter drives several motors (multi-motor drive).
• Start during motor run
Foot-mounted type, flange-mounted type
Totally-enclosed fan-cooled type (IP44)
-1
1750 min
0.4 to 75 kW
0 4 to 75 kW
0 4 to 55 kW
0.4 to 55 kW
1:10 (Variable torque) (Refer to * for constant output range.)
200V class: 200/208/220V 50Hz, 200/208/220/230V 60Hz
400V class: 400/415/440/460V 50/60Hz
+10% to -15%
Open loop vector
Digital command: 0.01%
Analog command: 0.05% (11 bit + code)
150% of rated output current for one minute
-10 to 10V, 0 to 10V, 4 to 20mA
0 to 6000 seconds
PID control, overtorque detection, torpue limit, multi-step speed operation,
accel/decel time change, 3-wire sequence, auto-tuning
Protected by electronic thermal overload relay
Motor coasts to a stop at approx. 200% of inverter rated current.
Motor coasts to a stop by blown-fuse.
Motor coasts to a stop after one minute at 150% of rated output current.
200V class: Motor coasts to a stop if main-circuit voltage exceeds 406V.
400V class: Motor coasts to a stop if main-circuit voltage exceeds 812V.
Protected by thermistor
Stall prevention during deceleration
Protected by electronic circuit
Charge LED stays ON until bus voltage drops below 50V.
Indoor (protected from corrosive gases and dust)
90% RH or less (non-condensing)
-20°C to +60°C
1000 m or less
2
9.8 m/s
(1G) at 10 to less than 20 Hz, up to 2 m/s
-1
1450 min
1:1.5 (0.4 to 55 kW)
1:1.3 (75 to 160 kW)
SSR1-
-1
1450 min
1150 min
0 4 to 45 kW
0.4 to 45 kW
Continuous
Class F
Without PG
± 5%
50%
1:10
± 0.2%
Provided
± 10%
2
(0.2G) at 20 to 50 Hz
1150 min
1:1.5 (0.4 to 45 kW)
1:1.3 (55 to 160 kW)
-1
-1