5.3
Wiring Notes for Robot Controller I/O Connectors (NPN
type)
After the wiring of the controller's I/O connectors is completed, check the following
before turning ON the power:
Check point (1)
Using a circuit tester, check across the "+24V terminal" and "0V terminal" of each
connector and across the "E24V terminal" and the "E0V terminal" to see that there is
no continuity. See the figure below and the table given on the next page.
Check point (2)
Using a tester, check across "each signal Output terminal" and "+24V terminal" or
"E24V terminal" of each connector to see that there is no continuity. See the figure
below and the table given on the next page.
Robot
controller
Caution: If the connector wiring between the Robot Controller's "+24V
terminal" and "0V terminal" and between the "E24V terminal"
and the "E0V terminal" is shorted, damage to the power circuit
of the Robot Controller will result.
Caution: If the wiring between "each signal Output terminal" and "+24V
terminal" or "E24V terminal" of each connector is shorted,
damage to the Output circuit and power circuit of the Robot
Controller will result.
Caution: Wind adhesive vinyl tape around all ends of the unconnected
wiring of each connector to prevent them from contacting other
wiring and parts, which results in shorting.
Checking Example
"+24V terminal" and
"E24V terminal" of the
controller
128
Circuit tester
External
device
"0V terminal" and
"E0V terminal" of
the controller