Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
MMR.S
MM
D.GAN
MA.DG
RM.NO
RM.DG
DMDC
RSET
APPENDIX A — DISPLAY TABLES (cont)
ITEM
DISPLAY
YES/NO
P.GAN
XX
I.GAN
XX.X
XX.X
MIN.S
XX
CRST
X
XX.XΔF
XXX.X °F
RM.F
XXX.X °F
XX.X °F
XXX.XΔF
RT.NO
XXX.XΔF
RT.F
RT.DG
XX.X °F
X
DM20
XXX%
SHNM
XXX
SHDL
XXX%
SHTM
XXX
DLS1
XXX%
DLS2
XXX%
LLEN
ENBL/DSBL
MSSL
SLVE/MAST
SLVA
XXX
LLBL
X
LLBD
XXX
LLDY
XXX
PARA
YES
ITEM DESCRIPTION
MOTORMASTER
Motormaster Select
Head Pressure P Gain
Head Pressure I Gain
Head Pressure D Gain
Minimum Fan Speed
RESET COOL TEMP
Cooling Reset Type
4-20 - Degrees Reset
Remote - No Reset Temp
Remote - Full Reset Temp
Remote - Degrees Reset
Return - No Reset Temp
Return - Full Reset Temp
Return - Degrees Reset
Demand Limit Select
Demand Limit at 20 mA
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Switch 1
Demand Limit Switch 2
Lead/Lag Chiller Enable
Master/Slave Select
Slave Address
Lead/Lag Balance Select
Lead/Lag Balance Delta
Lag Start Delay
Parallel Configuration
82
COMMENT
Default: NO
Default: 1
Range: 1 to 4
Default: 0.1
Range: -20 to 20
Default: 0.0
Range: -20 to 20
Default: 5
Default: 0
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 125 F
Range: 0° to125 F
Default: 0 F
Range: 0° to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 10.0 ΔF
Range: 0° to125 F
Default: 0 ΔF
Range: 0° to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 0
0 = None
1 = Switch
2 - 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
Range: 0 to 100%
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
Default: 60 minutes
Range: 0 to 120 minutes
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
Default: Disable
Default: Master
Default: 2
Range: 0 to 239
Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic
Default: 168 hours
Range: 40 to 400 hours
Default: 5 minutes
Range: 0 to 30 minutes
Default: YES (CANNOT BE
CHANGED)