APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS
PUMP OPTION
1, 8
2, 9
3, B
4, C
5, 6, D, F
7, G
PUMP SIZE
1.0 HP
1.5 HP
2.0 HP
3.0 HP
5.0 HP
7.5 HP
101
UNIT VOLTAGE
V-Hz (3 Ph)
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
OVERLOAD
SETTING
4.0
2.0
1.6
2.4
5.4
2.7
2.2
3.3
6.6
3.3
2.6
4.0
8.8
4.4
3.5
5.3
14.0
7.0
5.6
8.5
22.8
11.4
9.1
13.8