Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 Operation And Service Manual page 76

Air-cooled chillers with comfortlink controls
Hide thumbs Also See for AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060:
Table of Contents

Advertisement

SUB-MODE
ITEM
TEST
EXV.A
EXV.B
FAN1
FAN2
FAN3
FAN4
FAN5
OUTS
FAN6
V.HPA
V.HPB
CLP.1
CLP.2
UL.TM
CL.HT
RMT.A
CC.A1
CMPA
UL.TM
CC.A2
MLV
CMPB
CC.B1
CC.B2
SUB-MODE
ITEM
CEWT
CLWT
UNIT
OAT
SPT
DLWT
SCT.A
SST.A
CIR.A
RGT.A
D.GAS
SH.A
SCT.B
CIR.B
SST.B
RGT.B
SH.B
SUB-MODE
PRC.A
PRC.B
APPENDIX A — DISPLAY TABLES (cont)
Service Test Mode and Sub-Mode Directory
DISPLAY
xxx%
xxx%
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
xx
xx
ON/OFF
ON/OFF
xx
ON/OFF
ON/OFF
CIRCUIT A COMPRESSOR TEST
ON/OFF
xx
ON/OFF
ON/OFF
CIRCUIT B COMPRESSOR TEST
ON/OFF
ON/OFF
Temperature Mode and Sub-Mode Directory
DISPLAY
ENTERING AND LEAVING UNIT TEMPERATURES
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x ΔF
Pressures Mode and Sub-Mode Directory
ITEM
DISPLAY
DP.A
xxx.x PSIG
SP.A
xxx.x PSIG
DP.B
xxx.x PSIG
SP.B
xxx.x PSIG
76
ITEM DESCRIPTION
Service Test Mode
OUTPUTS
EXV % Open
EXV % Open
Fan 1 Relay
Fan 2 Relay
Fan 3 Relay
Fan 4 Relay
Fan 5 Relay
Fan 6 Relay
Var Head Press %
Var Head Press %
Cooler Pump Relay 1
Cooler Pump Relay 2
Comp A1 Unload Time
Cooler/Pump Heater
Remote Alarm Relay
Compressor A1 Relay
Comp A1 Unload Time
Compressor A2 Relay
Minimum Load Valve Relay
Compressor B1 Relay
Compressor B2 Relay
ITEM DESCRIPTION
Cooler Entering Fluid
Cooler Leaving Fluid
Outside Air Temperature
Space Temperature
Lead/Lag Leaving Fluid
TEMPERATURES CIRCUIT A
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
TEMPERATURES CIRCUIT B
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Suction Superheat Temp
ITEM DESCRIPTION
PRESSURES CIRCUIT A
Discharge Pressure
Suction Pressure
PRESSURES CIRCUIT B
Discharge Pressure
Suction Pressure
COMMENT
To enable Service Test mode, move
Enable/Off/Remote contact switch to
OFF. Change TEST to ON.
Move switch to ENABLE
COMMENT
COMMENT

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading